61
MYDENS
COSMOGAS
7 - USE
Parameter
Description of the parameter
Access
level
U.M.
Range
Factory
value
Customised
values
2130
Domestic hot water flow rate factor (N/A)
Installer
l/min
0...25,5
3,2
2131
Minimum central heating water pressure
Installer
bar
OFF 0,1...5,0
0,8
2132
Automatic filling hysteresis
Installer
bar
OFF 0,1...1,0
0,5
2133
Modulating pump temperature differential
Installer
°C
5...40
15
2134
Modulating pump ignition time
Installer
Sec
0...255
120
2135
Type of modulating pump
Installer
#
0 = Wilo Yonos;
1 = Salmson;
2 = Grundfos;
0
2136
Modulating pump mode
Installer
#
0 = Not modulating;
1 = Modulating;
2 = N/A;
3 = N/A;
4 = fixed speed at 40%;
5 = fixed speed at 50%;
6 = fixed speed at 60%;
7 = fixed speed at 70%;
8 = fixed speed at 80%;
9 = fixed speed at 90%;
10 = fixed speed at 100%;
10
2137
Minimum pump modulation power
Installer
%
0...100
40
2138
Fan speed map
Installer
#
50...55
50
2139
Air bleed function (N/A)
Installer
0...2
0
2140
Minimum heat exchanger water flow rate (Only for
2117
=
3
)
Installer
l/min/10 0...10
0,8
2141
Rated heat exchanger water flow rate (Only for
2117
=
3
)
Installer
l/min/10 0...10
4,3
2201
Enable/disable central heating
Installer
EnA = Enable;
dIS = Disabled
EnA
2202
Enable/disable domestic hot water
Installer
EnA = Enable;
dIS = Disabled
EnA
2203
Setting maintenance requests
Installer
ON = On;
OFF = Off;
RST = Reset;
OFF
2204
Days until maintenance request
Installer
days
30...1275
1000
2205
Frost protection
Installer
EnA = Enable;
dIS = Disabled
EnA
2206
Anti-legionella
Installer
EnA = Enable;
dIS = Disabled
EnA
2207
DHW detection delay
Installer
sec
0...255
1
N/A = Not applicable
(1)