4. Programming
72
496792
Notes:1. 13 Open and 14 Close provide the same functions as 4 Open/Close, but on
two separate channels.
2. 15 Zone omitted - the control unit sends this signal for five seconds when a
user omits a zone.
3. The control unit sends 08 RF Low Battery when the radio detector with a low
battery causes an alarm or sends a supervision signal. To enable this facility in
day mode set Menu 37 to option 1.
4. The control unit delays reporting/loging either mains loss, or exiting engi-
neering with mains loss, by 15-18 min (chosen randomly). If you chose a
Scandinavian default in Command 0 then the control unit waits at least 60
minutes before reporting.
Communication Acknowledge (Command 122)
Option 1 of this Command will be available if you select option
X
1 (Ireland) in
Command 0. In addition, the option is only effective if you have selected Scan-
com Fast format in Command 103.
Once the communicator has made a call and the ARC returned an acknowl-
edgement then with this Command enabled the keypad will display the
message “Call your CS” and beep for 10 seconds when the system is unset
or disarmed. To clear the display the user must enter a valid access code.
In addition, if you have used Command 121 to program channel 3 with Fast
Format communications then the control unit will add a 20 second delay
before dialling an alarm call.
To disable Communication Acknowledge use option 0.
Report Restorals (Command 123)
This option is only available if you have selected Scancom Fast format in
Command 103.
Restore off (0)
The system does not communicate restorals.
Restore on (1)
Enabled. The system will communicate restorals.
Reverse Open/Closed (Command 124)
Note: This Command is normally used in France.
This option is only available if you have selected Scancom Fast format. With
this option enabled the Open/Close Fast Format channel is reversed as
follows:
Option disabled
Option enabled
On setting system
False
True
On unsetting system
True
False
Note: This option does not afffect the separate Open channel and Close channel.