4. Programming
496792
43
To change:
Key-in:
Notes
Default
Note: The following Commands are available if you select option 1 for Com-
mand 89.
Confirm Timer
160
Y
nnn
nnn is a time in the range 001 to 999 minutes.
Default 030 minutes.
Internal Sounder
161
Y
0
Sounder on Unconfirmed Alarm
Y
1
Sounder on Confirmed Alarm
External Sounder
162
Y
0
Sounder on Unconfirmed Alarm
Y
1
Sounder on Confirmed Alarm
Confirmation After Entry
163
Y
0
Never
Y
1
One Zone
2
Two zones
User Reset After
164
Y
0
Disabled
Y
Confirmed Alarm
1
Enabled
Leaving Programming Mode
When all programming has been completed:
1.
Key-in ‘99
Y
’ at the keypad
The display shows:
99:Exit Eng ?
2.
Press
Y
.
The display shows:
99:Checking Sys
followed by the time and date.
The system is now in user mode.
Note: If there is a fault on the system , for example an open tamper circuit, the
display shows this and will not return to Day mode. Press
X
and rectify the
faults.
Engineer Reset
To perform an Engineer Reset:
1.
Check that the display is showing the alarm condition.
2.
Key in 0 followed by the Engineer’s code (default 7890), followed by 99
YY
.
The display shows the time and date.
Re-entering Programming Mode
You can go back into programming mode whenever the system is unset and
not in alarm:
1.
Key in 0 followed by the Engineer’s code (default 7890).
The display shows:
Installer Mode
You are now in programming mode.