background image

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will 

not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe 

components are the only types that can be worked on while live in the presence of a flammable 

atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts 

specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak.

8.Repair to intrinsically safe components 

 

and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and 

corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 

the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 

Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

brazing process.

10.Detection of flammable refrigerants

The following leak detection methods are deemed acceptable for systems containing flammable 

refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity 

may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a 

refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for 

the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

11.Leak detection methods

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or 

any other adverse environmental effects. The check shall also take into account the effects of aging or 

continual vibration from sources such as compressors or fans.

9.Cabling

Under no circumstances shall potential sources of ignition be used in the searching for or detection of 

refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

 

7.Repairs to sealed components 

  1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment 

   being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an 

   electrical supply to equipment during servicing, then a permanently operating form of leak detection 

   shall be located at the most critical point to warn of a potentially hazardous situation. 

   2)Particular attention shall be paid to the following to ensure that by working on electrical components, 

   the casing is not altered in such a way that the level of protection is affected. This shall include damage 

   to cables, excessive number of connections, terminals not made to original specification, damage to 

   seals, incorrect fitting of glands, etc.  Ensure that apparatus is mounted securely. Ensure that seals or 

   sealing materials have not degraded such that they no longer serve the purpose of preventing the 

   ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's 

   specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. 

Intrinsically safe components do not have to be isolated prior to working on them.

but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be 

reported to the owner of the equipment so all parties are advised.  

Initial safety checks shall include:  

That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking; 

That there no live electrical components and wiring are exposed while charging, recovering or purging 

the system; That there is continuity of earth bonding.

Safety 

Precautions

 Page 7

Summary of Contents for CH-STLS-14AC

Page 1: ...stallation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference MOBILE AIR CONDITIONER Loca...

Page 2: ...ns Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Ambient Temperature Range For Unit Operating Troubleshooting Tips 01 10 10 10 Energy...

Page 3: ...grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your unit...

Page 4: ...should be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the...

Page 5: ...t be performed by a certi ed technician Sociable Remark DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary It is pr...

Page 6: ...he air conditioner to avoid any damage or hazard Flammable Refrigerant R32 is used within air conditioner When maintaining or disposing the air conditioner the refrigerant R32 or R290 shall be recover...

Page 7: ...tion should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be sto...

Page 8: ...herently resistant to being corroded or are suitably protected against being so corroded 9 Checks to electrical devices The area shall be checked with an appropriate refrigerant detector prior to and...

Page 9: ...on sharp edges or any other adverse environmental e ects The check shall also take into account the e ects of aging or continual vibration from sources such as compressors or fans 9 Cabling Under no c...

Page 10: ...instructions h Do not over ll 13 Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of di erent refrigerants doe...

Page 11: ...the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Tran...

Page 12: ...for explanation purpose only Your machine may be slightly di erent The actual shape shall prevail The unit can be controlled by the unit control panel alone or with the remote controller This manual d...

Page 13: ...ts number means more cooling power for a larger room Be sure you are comparing only newer models to each other older models may appear to have a higher capacity but are actually the same Be sure to si...

Page 14: ...djustable window slider 1 Depending on the size of your window adjust the size of the window slider Use the combination of panels that best ts your window opening 2 If the length of the window require...

Page 15: ...ut side hole TYPE ONE Use the table below to determine what combinationof Window Sliders is correct for your window window slider window dimension mm window dimension inch a b 484 592 19 1 23 3 b c 59...

Page 16: ...rame see Fig 2 For some units attach the Window Kit Brace to the back of the hose panel to brace against the window so the window slider panels do not lean inward see Fig 3 3 Cut the non adhesive foam...

Page 17: ...hown see Fig 7 Foam seal B Adhesive type shorter Foam seal A Adhesive type Fig 7 2 Assembling the Sliding Window Adapter Only needed for Sliding Window applications Align both halves of the sliding wi...

Page 18: ...are installed in both sides of the window slider for improved rigidity 5 Cut the non adhesive foam seal C strip to match the window height Insert the foam seal between the glass and the window frame...

Page 19: ...lightly di erent than shown HEAT PUMP HOSE INSULATION FOAM only for heat pump mode NOTE When the unit is at heat mode the heat pump hose insulation foam must be xed in the hose of unit If you are expe...

Page 20: ...d angle Power Button Powers the unit on and o Operating Instructions Operating Instructions Control Panel Features NOTE The following control panels are for explanation purpose only The control panel...

Page 21: ...seconds again to stop the ION feature and the ION light turn dark the LED DISPLAY shows OF for 3 seconds for some units Sleep Button Used to initiate the SLEEP operation Pressing this button will inc...

Page 22: ...the desired time Press the TIMER button again within 5 seconds the Auto on start program is initiated And the TIMER ON indicator light illuminates Press the up or down button to select the desired Aut...

Page 23: ...t included can be attached to the adaptor if a longer hose length is required Place the end of the hose in the drain area you are using Water drainage During dehumidifying modes remove the upper drain...

Page 24: ...ill immediately stop However the fan motor will continue to operate this is normal Carefully move the unit to a drain location remove the bottom drain plug and let the water drain away Reinstall the b...

Page 25: ...nit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the applia...

Page 26: ...xhaust hose is not connected or is blocked There are heat sources inside the room Turn o the unit and clean the lter according to instructions Call a service technician to inspect the unit and top o r...

Page 27: ......

Page 28: ...Owner Name ____________________________________________________________________________________________ Address of Installation ________________________________________________________________________...

Page 29: ...urer for details THIS WARRANTY DOES NOT COVER Damages in shipping Damages caused by improper installation Damages as the result of not using product in accordance with provided instructions Damage fro...

Page 30: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servi...

Reviews: