NOTICE
• Do not use this device to turn the unit on or off.
• Always make sure the RESET button is pushed in for correct operation.
• The power supply cord must be replaced if it fails to reset when either the TEST button is
pushed, or it can not be reset. Please contact Customer Service.
16.Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended
good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, en-
sure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number
of cylinders for holding the total system charge is available. All cylinders to be used are designated for
the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refr-
igerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good
working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the
equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition,
a set of calibrated weighing scales shall be available and in good working order. Hoses shall be com-
plete with leak-free disconnect couplings and in good condition. Before using the recovery machine,
check that it is in satisfactory working order, has been properly maintained and that any associated
electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult
manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in
the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants
in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed,
ensure that they have been evacuated to an acceptable level to make certain that flammable refrig-
erant does not remain within the lubricant. The evacuation process shall be carried out prior to ret-
urning the compressor to the suppliers. Only electric heating to the compressor body shall be empl-
oyed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
Operation of Current Device
The power supply cord contains a current measuring device
that detects damage to the power cord. Test your power
supply cord as follows:
1. Plug in the air conditioner.
2. The power supply cord will have TWO buttons on the
plug head. Press the TEST button. You will notice a click as
the RESET button pops out.
3. Press the RESET Button. You will notice a click as the
button engages.
4. The power supply cord is now supplying electricity to
the unit. (On some products this is also indicated by a light
on the plug head.)
NOTICE
The power supply cord with this air conditioner contains
a current detection device designed to reduce the risk of
fire.
In the event that the power supply cord is damaged, it
can not be repaired. It must be replaced with a cord from
the manufacturer
Grounding type wall receptacle
Do not, under any
circumstances, cut,
remove or bypass
the grounding prong.
Power supply cord with 3-prong grou-
nding plug and current detection device.
Plug in & press RESET
Page 9
Installation
Instructions
Summary of Contents for CH-STLS-14AC
Page 27: ......