background image

 

 

    cylinders. (No more than 80 % volume liquid charge).i)  Do not exceed the maximum working 

    pressure of thecylinder, even temporarily.j)  When the cylinders have been filled correctly and the 

    process completed, make sure that the cylinders and the equipment are removed from site promptly 

    and all isolation valves on the equipment are closed off.k) Recovered refrigerant shall not be charged 

    into another refrigeration  system unless it has been cleaned and checked.

15.Labelling

    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The 

    label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment 

    contains flammable refrigerant.

Before carrying out this procedure, it is essential that the technician is completely familiar with the 

equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before 

the task is commenced. 

14.Decommissioning

a) Become familiar with the equipment and its operation.b) Isolate system electrically.c) Before 

attempting the procedure ensure that: Mechanical handling equipment is available, if required, for 

handling refrigerant cylinders;All personal protective equipment is available and being used correctly; 

The recovery process is supervised at all times by a competent person; Recovery equipment and 

cylinders conform to the appropriate standards.d) Pump down refrigerant system, if possible.e) If a 

vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of  the

system.f) Make sure that cylinder is situated on the scales before recovery takes place.g) Start the 

recovery machine and operate in accordance with manufacturer's instructions.h) Do not overfill 

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure

that contamination of different refrigerants does not occur when using charging equipment. Hoses or 

lines shall be as short as possible to minimise the amount of refrigerant contained in them. 

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior 

to commissioning. A follow up leak test shall be carried out prior to leaving the site.

12.Removal and evacuation

    When breaking into the refrigerant circuit to make repairs or for any other purpose conventional 

    procedures shall be used. However, it is important that best practice is followed since flammability is 

    a consideration. The following procedure shall be adhered to:

    Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the 

    circuit by cutting or brazing.  

    The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flu-

    shed with OFN to render the unit safe. This process may need to be repeated several times. Comp-

    ressed air oroxygen shall not be used for this task. 

    Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until 

    the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. 

    This process shall be repeated until no refrigerant is within the system. When the final OFN charge is 

    used, the system shall be vented down to atmospheric pressure to enable work to take place. This 

    operation is absolutely vital if brazing operations on the pipe-work are to take place. 

    Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventila-

    tion available.

Safety 

Precautions

 Page 8

 

Summary of Contents for CH-STLS-14AC

Page 1: ...stallation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference MOBILE AIR CONDITIONER Loca...

Page 2: ...ns Air Filter Cleaning Troubleshooting Tips Unit Cleaning Store the unit when not in use Preparation Design Notice Ambient Temperature Range For Unit Operating Troubleshooting Tips 01 10 10 10 Energy...

Page 3: ...grounded and has the appropriate voltage The power cord is equipped with a three prong grounding plug to protect against shock Voltage information can be found on the nameplate of the unit Your unit...

Page 4: ...should be supervised to ensure that they do not play with the appliance Children must be supervised around the unit at all times be applicable for other countries except the European Countries If the...

Page 5: ...t be performed by a certi ed technician Sociable Remark DISPOSAL Do not dispose this product as unsorted municipal waste Collection of such waste separately for special treatment is necessary It is pr...

Page 6: ...he air conditioner to avoid any damage or hazard Flammable Refrigerant R32 is used within air conditioner When maintaining or disposing the air conditioner the refrigerant R32 or R290 shall be recover...

Page 7: ...tion should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge The maximum number of pieces of equipment permitted to be sto...

Page 8: ...herently resistant to being corroded or are suitably protected against being so corroded 9 Checks to electrical devices The area shall be checked with an appropriate refrigerant detector prior to and...

Page 9: ...on sharp edges or any other adverse environmental e ects The check shall also take into account the e ects of aging or continual vibration from sources such as compressors or fans 9 Cabling Under no c...

Page 10: ...instructions h Do not over ll 13 Charging procedures In addition to conventional charging procedures the following requirements shall be followed Ensure that contamination of di erent refrigerants doe...

Page 11: ...the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder and the relevant Waste Tran...

Page 12: ...for explanation purpose only Your machine may be slightly di erent The actual shape shall prevail The unit can be controlled by the unit control panel alone or with the remote controller This manual d...

Page 13: ...ts number means more cooling power for a larger room Be sure you are comparing only newer models to each other older models may appear to have a higher capacity but are actually the same Be sure to si...

Page 14: ...djustable window slider 1 Depending on the size of your window adjust the size of the window slider Use the combination of panels that best ts your window opening 2 If the length of the window require...

Page 15: ...ut side hole TYPE ONE Use the table below to determine what combinationof Window Sliders is correct for your window window slider window dimension mm window dimension inch a b 484 592 19 1 23 3 b c 59...

Page 16: ...rame see Fig 2 For some units attach the Window Kit Brace to the back of the hose panel to brace against the window so the window slider panels do not lean inward see Fig 3 3 Cut the non adhesive foam...

Page 17: ...hown see Fig 7 Foam seal B Adhesive type shorter Foam seal A Adhesive type Fig 7 2 Assembling the Sliding Window Adapter Only needed for Sliding Window applications Align both halves of the sliding wi...

Page 18: ...are installed in both sides of the window slider for improved rigidity 5 Cut the non adhesive foam seal C strip to match the window height Insert the foam seal between the glass and the window frame...

Page 19: ...lightly di erent than shown HEAT PUMP HOSE INSULATION FOAM only for heat pump mode NOTE When the unit is at heat mode the heat pump hose insulation foam must be xed in the hose of unit If you are expe...

Page 20: ...d angle Power Button Powers the unit on and o Operating Instructions Operating Instructions Control Panel Features NOTE The following control panels are for explanation purpose only The control panel...

Page 21: ...seconds again to stop the ION feature and the ION light turn dark the LED DISPLAY shows OF for 3 seconds for some units Sleep Button Used to initiate the SLEEP operation Pressing this button will inc...

Page 22: ...the desired time Press the TIMER button again within 5 seconds the Auto on start program is initiated And the TIMER ON indicator light illuminates Press the up or down button to select the desired Aut...

Page 23: ...t included can be attached to the adaptor if a longer hose length is required Place the end of the hose in the drain area you are using Water drainage During dehumidifying modes remove the upper drain...

Page 24: ...ill immediately stop However the fan motor will continue to operate this is normal Carefully move the unit to a drain location remove the bottom drain plug and let the water drain away Reinstall the b...

Page 25: ...nit using a damp lint free cloth and mild detergent Dry the unit with a dry lint free cloth Drain the unit s water collection tray according to the instructions in the following section Run the applia...

Page 26: ...xhaust hose is not connected or is blocked There are heat sources inside the room Turn o the unit and clean the lter according to instructions Call a service technician to inspect the unit and top o r...

Page 27: ......

Page 28: ...Owner Name ____________________________________________________________________________________________ Address of Installation ________________________________________________________________________...

Page 29: ...urer for details THIS WARRANTY DOES NOT COVER Damages in shipping Damages caused by improper installation Damages as the result of not using product in accordance with provided instructions Damage fro...

Page 30: ...and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the servi...

Reviews: