29
Operator Interface
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
Multi-Unit Operation Tab, continued...
–
Sequence Interval:
allows you to set the time interval used by
the control software to establish a new operating sequence to
balance operating hours of linked humidifiers.
Note:
This set-
is enabled.
Setting range:
24-1000 hours
Factory setting:
24 hours
–
Linkup Timeout:
allows you to set the maximum time limit
that the units in the Linkup chain can operate without com
-
munication to each other before a timeout warning message is
generated.
Setting range:
6
0-120 seconds
Factory setting:
60 seconds
–
Zero Out:
shows the percentage value of the system demand
signal at which the unit is switched on.
Setting range:
0-100%
Factory setting:
0%
Note:
This setting can only be modified if more than one unit is
physically connected to the Linkup chain.
–
Full Out:
shows the percentage value of the system demand
signal at which the unit achieves 100% demand.
Setting range:
0-100%
Factory setting:
100%
Note:
This setting can only be modified if more than one unit is
physically connected to the Linkup chain.
Refer to
"Configuring for Multi-Unit Operation" on page 40
procedure.