39
Operator Interface
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
Software Settings Tab
–
Load Contact Info Page:
allows you to automatically insert contact
information (for technical support) in the unit, from a USB memory
stick. This information is shown when selecting Help on the Home
Screen. Information includes Company Name, Address, Telephone
Number, Email, and Website. Please contact your Condair representa
-
tive for assistance with this.
–
Manually Load Contact Info:
allows you to manually enter the
Company Name, Address, Telephone Number, Email, and Website,
that will appear when the user selects Help from the Home Screen.
–
Load Logger Definition:
allows you to load a logger definition file
from a USB drive to save data (CSV file) on the USB while the unit
is functioning. A factory supplied access file is required to enable
operation. The interval between recordings can be changed from
the Engineering menu (see your Condair representative).
–
Backup Parameters to USB:
saves the current value of all persis
-
tent parameters from a certain integrated controller to USB (XML
file).
–
Restore Parameters from USB (selected):
loads the persistent
paramters (XML file) from USB to an integrated controller.
–
Restore Factory Defaults
: Return the GS software settings to
values set at the factory.
4.3
Software Configuration
The Condair
GS humidifier is shipped fully configured from the factory to suit your site-specific require
-
ments, but this can be modified as needed. This section provides the necessary instructions to recon
-
figure the control software.
4.3.1
Configuring the Control Software
Perform the basic setup of the control software as follows, if necessary:
1. Make sure that all control wiring and jumpers are installed as described in "External Connections"
in the Installation Manual.
2. Set up the following parameters:
– select the type of control signals to the humidifier ("Analog", "Modbus", "BACnet/IP", etc.,).
Select "Analog" if a sensor/transducer signal or a demand signal from an external P/PI (pro
-
portional)/(proportional-integral) controller is wired directly to the humidifier. Otherwise, select
an applicable digital communication protocol from the list. If your humidifier has the optional
Lonworks or BACnet (BTL) module installed, select "Modbus".
– select the number of control channels.
Select "Dual" if controlling the humidifier with a high limit and a control signal; otherwise set to
"Single".
– select the general control mode for the incoming control and high limit signal ("De
-
mand", "RH P", "RH PI", or "On/Off").
Select "Demand" if the control signal is a demand signal from an external controller. Select "RH
P" or "RH PI", as appropriate, if the control signal is from a sensor/transducer. Or select "On/
Off" if the control signal is from an external On/Off humidistat.
Signal Type – select the signal type of the incoming control signal if
-
mand", "RH P" or "RH PI", and signal