60
Fault Isolation
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
Problem
Probable Cause
Humidifier will not produce
steam, or does not reach RH
setpoint value.
Safety loop is open.
– Check if the message “Safety Loop” is displayed in the operating status area of the Home
screen.
– Check if there is 24 VAC supply at low voltage terminal strip pin “2”.
– Check that all On/Off devices connected to low voltage terminal strip pins “1” and “2” are
wired properly, and their contacts are closed when they should be.
Output is limited by the high limit humidistat signal.
– Check if the high limit humidistat is installed too close to the steam distributor. The recom
-
mendation is five times the absorption distance or minimum 3 m. Check the setpoint value
for the high limit – typically set at 80% RH.
No signal on Channel 1.
– Check voltage between low voltage terminal strip pins “3” and “4”. For a demand signal
configuration, the signal must be 27% of full scale signal for the humidifier to start. For a
transducer signal configuration, the signal must be lower than the setpoint value for the
humidifier to start.
No signal on Channel 2 (on units with
set to "Dual").
– Check voltage between low voltage terminal strip pins “3” and “5”. For a demand signal
configuration, the signal must be 27% of full scale signal for the humidifier to start. For a
transducer signal configuration, the signal must be lower than the setpoint value for the
humidifier to start.
Capacity has been manually limited.
, if necessary.
Humidifier displays warning
or fault message.
The control software has detected an abnormal condition.
–
"Warning and Fault List" on page 60
.
7.4
Warning and Fault List
shows the list of warning and fault messages triggered by the control software in the humidi
-
fier, and the corrective actions. The warning code escalates to a fault code if the alarm condition is not
resolved within a certain period of time. After fixing a fault condition, reset the fault status as described
in
"Resetting Fault Status" on page 66
.
Table 14: Warning and Fault List
Code
Message
Probable Cause
Warning
Fault
W01
E01
Smartcard miss
-
ing
No communication with the SIM card.
The SIM card may not be seated properly on the integrated control board.
Check that the SIM card is seated properly.
Defective SIM card.
Contact your Condair representative.
W06
–
Main Unit Miss-
ing
(or)
Extension Miss-
ing
(No Signal
Warning)
No communication between the Extension unit and the Main unit in the Linkup chain.
Operation is interrupted until a signal is received.
The Linkup configuration between the Main and Extension unit is not set correctly.
– Check the Linkup configuration.
The Main unit or Extension unit may be switched off.
– Switch on the Main and/or Extension unit.
Loose connection.
– Check the connection between the Main and Extension units.
W07
–
Ext Fault
An Extension unit has a fault condition which was communicated to the
Main unit.
Alarm condition in the Extension
unit(s).
– Check the Extension unit(s).
–
E10
CTRLR Fault
(or)
Memory
(or)
CTRLR Reset
Flash memory read/write fault.
– Contact your Condair representative.