FTBD (Full Tank Blowdown):
allows you to enable or disable the
full tank blowdown function. Depending on the water quality, this
function can be used to extend operational life and service inter
-
vals by reducing mineral build-up in the tank. When enabled, the
FTBD function performs a full drain of the tank when the weighted
. When blowdown is com
-
pleted, the tank is refilled and the unit resumes normal operation.
Options:
On
or
Off
Factory setting:
On
–
FTBD Time:
allows you to set the time of day when a full tank
blowdown will occur.
–
FTBD Interval:
allows you to set the frequency of full tank blow
-
downs in weighted hours (equivalent to a unit operating at 100%
output). Refer to
"Adjusting Blowdown Settings" on page 49
for addi-
tional details.
Setting range:
1-200 hr
Factory setting:
100 hr
–
Fill Correction 1:
allows you to adjust all the parameters for the
high volume fill valve(s) to compensate for valve tolerances, as
well as site-specific conditions.
CAUTION!
Do not adjust this value unless instructed to
do so by a Condair representative.
Setting range:
0.1-10.0
Factory setting:
1.0
–
Fill Correction 2:
allows you to adjust all the parameters for the
low volume fill valve(s) to compensate for valve tolerances, as well
as site-specific conditions.
CAUTION!
Do not adjust this value unless instructed to
do so by a Condair representative.
Setting range:
0.1-10.0
Factory setting:
1.0
–
Drain Correction:
allows you to adjust all the parameters used for
draining the tank and blowdowns to compensate for drain pump
flow rates and site-specific conditions.
CAUTION!
Do not adjust this value unless instructed to
do so by a Condair representative.
Setting range:
0.5-1.5
Factory setting:
1.0