43
Operation
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
5.2.4 Remote Monitoring
The Condair
GS humidifier can be monitored remotely through the remote fault board wired to a remote
describes the function of each relay when triggered.
Table 7: Remote Relay Function
Remote Relay
Description
Error
The humidifier is stopped due to a fault condition, or may be oper
-
able only for a limited period of time.
Service/Warning
Depending on the software configuration, indicates that a service
warning or a system warning/notification is active.
Unit On
The humidifier has power, and the On/Off switch is in the On
position.
The Condair
GS humidifier can also be monitored remotely from a laptop or desktop computer using
the ethernet port on the integrated control board. Contact your Condair representative for assistance.
5.2.5 Inspections During Operation
Perform regular inspection of the
Condair
GS humidifier and the humidification system when it is in
operation. Inspect the following:
Check the gas connection for any leaks.
Check the water, drain and steam connections for any leakages.
If applicable, check the humidifier and other system components have not shifted from their mount
-
ings, and are fastened securely.
Check for leaks in the exhaust vent. Check that there are no obstructions anywhere in the exhaust
vent, including the exhaust terminal.
Keep the area around the air intake in the unit clear of all obstructions. If an air intake vent is used,
check for leaks and obstructions in the vent, including the intake terminal.
Check the area around the unit is clear of all insulating and combustible materials.
Visually check the electrical wiring for any damage.
Check the Home screen on the humidifier for service or system warning messages.
If any irregularities (leakages, fault messages or damaged components) are found, shut down the
Condair
GS humidifier before performing service – refer to
. Contact your Condair rep
-
resentative if assistance is required.