6.5.4 Cleaning the Float Chamber
Clean the float chamber in the fill box as follows. Refer to
1. Shut down the humidifier as described in
and remove the side panel – refer
"Removal and Installation of Access Panels" on page 50
2. Remove hoses from the float chamber, and remove the float chamber by pulling on the rear tab and
lifting the float chamber upwards.
3. Open the float chamber and carefully remove the two floats. Make a note of the orientation of the floats.
4. Use a soft-bristled brush (not wire brush) to remove all scale build-up on the floats, the inside of the
float sleeve and the float chamber. Rinse with clean tap water.
5. Visually check each float for cracks or other damage. Place the two floats in a container filled with
clean water, and check that they both have equal buoyancy. If necessary, replace the floats.