Fault Isolation
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
7
Fault Isolation
7.1
General
Troubleshooting of the
Condair
GS humidifier must only be performed by well qualified and well trained
personnel. Electrical repairs must only be performed by a licensed electrician authorized by the customer
or by Condair service technicians.
Troubleshooting the
Condair
GS humidifier may require personnel to access the inside of the control
cabinet in the humidifier which may expose personnel and equipment to the hazards described in
.
7.2
Fault Indication
When a condition that is not normally expected occurs, it is detected by the control software and a warn
-
ing or fault message is displayed in the Service/Warning/Fault status area of the Home screen (refer to
). The warning and fault message types are described in
When a warning/fault condition occurs, select the warning or fault message to view the
and additional details. Refer to
Figure 16: Fault History Screens
In addition, the Service relay in the remote fault board can also be set up to indicate that a service warn
-
ing or a system warning/notification is active.
7.3
General Troubleshooting
Most operational warning/fault conditions are caused by improper installation, or by not adhering
to the suggested best practices for installation of the humidifier and system components
. Hence,
a full fault diagnosis always requires a thorough examination of the entire system (hose connections,
control systems, etc.).
provides general guidelines for troubleshooting the humidifier. For detailed troubleshooting in
-
formation of the auxiliary system components, refer to their product manuals.
The list of warning and fault messages, and corrective actions are shown in
Table 13:
General Troubleshooting – Humidifier
Problem
Probable Cause
Nothing happens when the
On/Off switch is turned On.
Incorrect voltage, or no voltage.
– Check the disconnect switch in the supply line.
– Check the fuse between the transformer and the On/Off switch.
Step-down transformer not outputting 24 VAC.
– Check the fuse.
– Measure and confirm 24 VAC on the transformer primary connections. Replace the trans
-
former, if necessary.