32
Operator Interface
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
BMS Timeout Tab
–
BMS Timeout:
allows you to set the maximum time the humidifier
will wait without any communications from the BMS network before
a timeout warning is generated.
Setting range:
1-300 seconds
Factory setting:
300 seconds
Modbus Parameters Tab
–
Modbus:
allows you to enable or disable the Modbus communica
-
tions protocol. Enabling or disabling Modbus always requires a
power cycle of the unit.
Options:
On, Off, RTU (one connection via RS-485),
or TCP (4 concurrent connections, only
slave ID255-supported Modbus TCP is imple-
mented by the same stack as Modbus RTU)
Factory setting:
On
The following settings appear only if
is enabled.
–
Modbus Address
: allows you to set the Modbus address of the
humidifier on the network.
Setting range:
1-247
Factory setting:
10
–
Parity
: allows you to set the parity bit for the data transfer.
Options:
None, Even
or
Odd
Factory setting:
Even
–
Baudrate
: allows you to set the baudrate for the data transfer.
Options:
110, 300, 600, 1200, 2400, 4800, 9600,
19200, 38400, 57600, 76800 or 115200
Factory setting:
9600
BACnet Parameters Tab
–
BACnet:
allows you to enable or disable the BACnet communica
-
tions protocol. Enabling or disabling BACnet always requires a
power cycle of the unit.
Options:
BACnet/IP
– enables BACnet/IP over the
RJ45 (Ethernet) interface
.
MSTP
– enables BACnet MSTP over the
RS485 interface.
Note:
The Condair GS hu-
midifier is a slave-only BACnet MSTP device.
Off
– disables BACnet communications
protocol.
Factory setting:
Off