Maintenance
Condair GS
xxxxxxx_A_EN_1905_Condair-GS_OM
6. Reassemble the float chamber, ensuring the orientation of the floats have been maintained, and
opposing poles are facing up (one positive, one negative pole). Reinstall it to the bracket on the
humidifier and reconnect hoses. Refer to
7. Re-start the humidifier – refer to
"Restarting After Shutdown" on page 45
and ensure that the Float Check
is enabled in the features menu – refer to
.
8. Check for leaks.
1
2
3
4
5
6
7
8
Figure 12: Cleaning Float Chamber
1
Bracket, float chamber and P-trap
2 Float chamber
3
Tab, float chamber
4 Float (x2)
5
Seal, float chamber
6 Screw (x3)
7 Hose, to bottom of tank
8 Hose, to top of tank
6.5.5 Cleaning Hoses, Dual Fill Valves and Drain Pump
Clean the fill and drain hoses, the dual fill valves, and the drain pump as follows. Refer to
.
1. Shut down the humidifier as described in
.
2. Remove the side panel – refer to
"Removal and Installation of Access Panels" on page 50
.
3. Loosen the clamps and remove the fill and drain hoses from the humidifier.
4. Carefully remove the strainer in the dual fill valves. Use a soft-bristled brush (not wire brush) and
carefully remove any scale build-up on the strainer in the dual fill valves. Assemble the dual fill valves
after cleaning, taking care not to damage the strainer.
5. Remove the setscrew, and rotate the drain pump assembly to disengage it from the drain fitting.
Rotate and separate the pump cover from the pump housing. Use a soft-bristled brush (not wire
brush) to remove any scale build-up on the inside of the pump cover, impeller, large O-ring and pump
housing. Assemble all drain pump components in reverse order after cleaning. Install the pump as
-
sembly in the drain fitting, making sure that the small O-ring is installed in the drain fitting. Secure
the drain pump in place with the setscrew.
6. Use a rubber mallet to knock out any scale build-up in the fill and drain hoses. Rinse the hoses
thoroughly with hot tap water before installing the hoses. Secure the hoses with clamps.
7. Re-start the humidifier – refer to