background image

 

Section 1 

An Introduction to Dielectric Withstand Testing with the HT-3000P 

 

 

The continuity test/dielectric withstand test is a production line test which is recognized 

by  safety  agencies  worldwide  as  a  valid  criterion  of  safe  assembly  of  end-use  equipment.  The 
test  ensures  that  the  primary  circuit  power  and  ground  conductors  were  properly  wired  and 
connected for safe operation.  It also applies a high-voltage potential between power and ground 
conductors to make sure that no unintentional leakage or arcing paths exist between power and 
ground.    The  test  consists  of  a  ground  continuity  check,  a  leakage  current  check  and  a  high 
voltage  check.    It  is  non-destructive  to the equipment under test, and can be accomplished in a 
short time.   

 

Safety Precautions 

 
 

The dielectric withstand test generates voltages of up to 2000 volts AC or 2800 volts DC 

at potentially lethal current levels.  Currents of as little as 5 mA at 120 volts can cause death, and 
the HT-3000 is capable of generating 20 mA AC at up to 2000 volts, and 5 mA DC at up to 2800 
volts.    The  HT-3000  has  been  designed  to  minimize  exposure  to  high  voltages.    However,  the 
potential for serious injury or death exists and personnel should be aware when they conduct this 
test. 

 

Test Personnel 

 
 

Personnel require special training to conduct the dielectric withstand test.  They should 

understand electrical fundamentals clearly, and be aware that high voltage is adept and creative 
at completing a path to ground.  Instructions should include a warning against any metal jewelry.  
Operators should not allow others in the testing area, especially when tests are being conducted.  
Organization  is  to  be  stressed.    The  operator  should  keep  the  area  free  of  unused  leads  and 
equipment. 

 

Testing Area 

 

 

The area used for conducting the dielectric withstand test should be as remote as possible 

from  normal  production  line  activities.    Only  personnel  actually  conducting  the  test  should  be 
allowed  in  the  area,  and  it  should  be  taped  or  roped  off  to  preclude  casual  entry  by  other 
employees.  In addition, the area should be marked "WARNING - HIGH VOLTAGE TESTING" 
or the equivalent to warn others of the nature of the testing taking place.   
 

The bench being used should be non-conductive, and any exposed metal parts should be 

tied together and grounded.  If a conductive surface must be used, it should be grounded. 
 

Because  of  sparking  during  a  dielectric  test  failure,  it  is  not  safe  to  conduct  dielectric 

withstand tests in combustible atmospheres. 
 

It is imperative that a good ground be provided to the HT-3000P.  Before connecting the 

HT-3000P,  ensure  that  a  low-resistance  ground  is  provided  by  the  building  wiring.    If  the  HT-
3000P is used on a high-resistance grounding circuit, dangerous high voltages may be present to 
the  operator.    In  addition,  the  power  to  the  Testing  Area  should  be  provided  with  an  easily 
reached shutoff switch which can be actuated by personnel outside the Area if needed. 

Summary of Contents for HT-3000P

Page 1: ...HT 3000P Dielectric Withstand Tester 0 2000 Volts AC Output 0 2800 Volts DC Output Instruction Manual COMPLIANCE WESTUSA...

Page 2: ......

Page 3: ...logic controlled circuit design and ergonomic front panel and represents the latest in high voltage production line testing To fully appreciate all the features of your new meter we suggest that you t...

Page 4: ...2...

Page 5: ...and Rear Panel Features 11 Initial Checkout Procedure 16 Setting up the HT 3000P for Production Line Testing 17 Factory Settings 17 Display of Leakage Limit and Duration settings 17 Adjustment of the...

Page 6: ...ndamentals clearly and be aware that high voltage is adept and creative at completing a path to ground Instructions should include a warning against any metal jewelry Operators should not allow others...

Page 7: ...tion between the operator and the test being conducted The HT 3000P is designed to bleed the high voltage away after the test has concluded In order to ensure that any voltage present in the equipment...

Page 8: ...continuously during the test When testing with the Ground Check switch in the Off position the operator must ensure that the Test Return Lead is properly connected to exposed dead metal of the equipme...

Page 9: ...s is due to the AC voltage charging all capacitors connected between primary voltage and ground If the overall value of these capacitors cause a leakage current of more than 20 mA to flow at the desir...

Page 10: ...ntil the voltage has discharged to a safe level to protect the operator and also to ensure that there is no energy stored in the tested equipment Testing Equipment with non Standard Plugs or Pigtail O...

Page 11: ...ff by a resistor bank in the HT 3000P The voltage discharge progress is shown by the front panel meter Failure modes are shown by the front panel LED s for quick troubleshooting Convenience and testin...

Page 12: ...available by removing adjustment shafts ENVIRONMENTAL Operating Temperature 15 40 C Relative Humidity Range 0 90 non condensing GENERAL Input power requirements See rear panel for input voltage and f...

Page 13: ...ock absorbing material on all sides of the container Remove the tester from its container and place it on a test bench AC Line Voltage Requirements AC line voltage requirements for your Tester are not...

Page 14: ...11 Figure 2 Controls Indicators Connectors Model HT 3000P Front Panel...

Page 15: ...d the test will be terminated 5 Full Voltage LED If full voltage is successfully reached the Full Voltage LED will light and the high voltage duration timer starts 6 Hipot Fail LED Indicates failure o...

Page 16: ...13 Figure 3 Controls Indicators Connectors Model HT 3000P Rear Panel...

Page 17: ...ent of the High Voltage Ramp Time for this procedure 4 Test Time Adjustment Used to adjust high voltage test duration See Adjustment of the High Voltage Test Duration section for this procedure 5 Leak...

Page 18: ...15...

Page 19: ...osition 8 Verify that all test leads are disconnected from the HT 3000P 9 Push the red RESET button then the yellow TEST button 10 The tester should sound the buzzer The red Ground Open and red RESET...

Page 20: ...may light and in some instances the Ground OK LED may extinguish Passage of these tests indicates that the HT 3000P is functioning properly and that it is safe to use If the results of the performanc...

Page 21: ...ons Use this procedure if adjustment to a different ramp time within the range of 1 5 seconds is required 1 Defeat the Ground Check by turning the rear panel switch to the Off position 2 Connect the H...

Page 22: ...the rear panel turn the Test Time potentiometer As soon as the potentiometer starts turning the meter will display d and the value can be set in 1 second increments from 1 to 60 seconds 4 If tamperpro...

Page 23: ...e power switch to the I or ON position Push the RESET button The yellow TEST indicator should light indicating that the HT 3000P is ready to test 2 Connect the HTT 1 to the HT 3000P tester using the c...

Page 24: ...f time set in the Test Duration procedure If a breakdown of the insulation system between primary voltage and ground is detected the red Hipot Fail LED will light the buzzer will sound and the test wi...

Page 25: ...ssistance Phone 800 748 6224 Technical Assistance is available from Compliance West USA between the hours of 8 30 AM and 4 30 PM Pacific Time Compliance West USA 2120 Jimmy Durante Blvd Suite 118 Del...

Page 26: ...23...

Page 27: ...ad with a banana plug on one end are required to conduct the performance test The test equipment required for the calibration procedure is a DMM able to read true rms 0 2000 Vac 1 0 2800 Vdc 1 and a 3...

Page 28: ...the front panel and case with a mild solution of detergent and a damp sponge Clean dust from the PWB with clean dry low pressure 20 psi Calibration Procedure The Calibration Procedure should be perfo...

Page 29: ...r clip end to the 3 ohm resistor 3 Connect the banana plug end of the other lead to the round grounding jack of the DEVICE receptacle and the alligator clip end to the 3 ohm resistor 4 Turn the Ground...

Page 30: ...a test and using the 1000 1 voltage probe to check the meter at different voltages If the voltages are not within 2 at each voltage the voltage calibration must be performed again starting at step 1 a...

Reviews: