background image

 

the Test Return Lead clip from the equipment under test and reconnecting it, taking care to make 
a  good  connection.    The  unit  should  then  be  retested.    If  a  failing  result  is  repeated,  the 
connection  between  the  power  supply  cord  ground  pin  and  the  chassis  of  the  equipment  being 
tested should be checked and reworked until a passing result is obtained. 
 

 

*Special calibrations available by internal adjustment.  Must be performed by qualified service 

personnel.  See Sec. 5. 

 

Defeating the Ground Check 

 

 

The  Ground  check  can  only  be  conducted  on  equipment  using  a  three  wire  grounded 

power supply cord.  Some equipment, such as most portable lamps and all double insulated tools, 
have only a two wire power supply cord, so the Ground test cannot be conducted.   
 
 

Please  note  that  defeating  the  Ground  check  should  not  be  done  except  when 

necessary  to  test  two-wire  devices.    The  Ground  check  feature  provides  an  extra  level  of 
operator  safety  because  high  voltage  will  not  be  applied  if  the  Test  Return  Lead  is  not 
properly  connected  to  the  exposed  dead  metal  of  the  equipment  being  tested.    If  the  Test 
Return Lead is not properly connected, a dielectric withstand failure may energize exposed 
dead  metal.    Additionally,  the  HT-3000P  may  not  recognize  the  failure.    The  test  will 
continue for its normal length of time, and the HT-3000P may show a "PASS". 

 
 

To  allow  the  HT-3000P  to  test  equipment  using  a  two  wire  power  supply  cord,  the 

Ground  Check  can  be  defeated  by  turning  the  rear  panel  Ground  Check  switch  to  the  Off 
position.  To remind the operator that the Ground Check is not being conducted, both the green 

Ground OK

 and red 

Ground Open

 LED's will be lit continuously during the test.  When testing 

with the Ground Check switch in the Off position, the operator must ensure that the Test Return 
Lead is properly connected to exposed dead metal of the equipment being tested for safety and to 
ensure that the HT-3000P properly reports all failures. 
 

Leakage Test 

 
 

The HT-3000P leakage test uses a separate low-frequency circuit to check for excessive 

leakage between primary power components and ground.  There is not a specific leakage current 
level pass/fail requirement at this time for most equipment, however, higher than normal leakage 
current  on  a  particular  part  may  indicate  an  assembly  or  component  problem  in  the  primary 
circuit.   
 

The leakage current is also monitored by the HT-3000P to ensure that excessive leakage 

does not keep the tester from developing full voltage required for the high voltage test.  The HT-
3000P will provide full voltage at any leakage current level up to 20 mA AC or 5mA DC.  The 
leakage current trip level is adjustable on the rear panel.   
 

The leakage test is conducted by shorting the power and neutral conductors of the power 

supply cord and applying high voltage between them and the exposed dead metal of the chassis 
of the equipment being tested. 
 

Excessive  leakage  current  is  not  grounds  for  failure  of  the  dielectric  withstand  test.  

Leakage current is a normal result of capacitance in the primary circuit between neutral or line 
conductors and ground.  (In dielectric tests of some larger electric motors, leakage currents of as 
high as 95 mA are considered acceptable by safety agencies.)  However, leakage currents higher 
than normally anticipated for a particular model should not be ignored.  This indicates problems 
of  low  resistance  up  to  a  short  circuit  between  line/neutral  and  ground,  and  failures  should  be 
investigated.  Failure modes are discussed below. 

Summary of Contents for HT-3000P

Page 1: ...HT 3000P Dielectric Withstand Tester 0 2000 Volts AC Output 0 2800 Volts DC Output Instruction Manual COMPLIANCE WESTUSA...

Page 2: ......

Page 3: ...logic controlled circuit design and ergonomic front panel and represents the latest in high voltage production line testing To fully appreciate all the features of your new meter we suggest that you t...

Page 4: ...2...

Page 5: ...and Rear Panel Features 11 Initial Checkout Procedure 16 Setting up the HT 3000P for Production Line Testing 17 Factory Settings 17 Display of Leakage Limit and Duration settings 17 Adjustment of the...

Page 6: ...ndamentals clearly and be aware that high voltage is adept and creative at completing a path to ground Instructions should include a warning against any metal jewelry Operators should not allow others...

Page 7: ...tion between the operator and the test being conducted The HT 3000P is designed to bleed the high voltage away after the test has concluded In order to ensure that any voltage present in the equipment...

Page 8: ...continuously during the test When testing with the Ground Check switch in the Off position the operator must ensure that the Test Return Lead is properly connected to exposed dead metal of the equipme...

Page 9: ...s is due to the AC voltage charging all capacitors connected between primary voltage and ground If the overall value of these capacitors cause a leakage current of more than 20 mA to flow at the desir...

Page 10: ...ntil the voltage has discharged to a safe level to protect the operator and also to ensure that there is no energy stored in the tested equipment Testing Equipment with non Standard Plugs or Pigtail O...

Page 11: ...ff by a resistor bank in the HT 3000P The voltage discharge progress is shown by the front panel meter Failure modes are shown by the front panel LED s for quick troubleshooting Convenience and testin...

Page 12: ...available by removing adjustment shafts ENVIRONMENTAL Operating Temperature 15 40 C Relative Humidity Range 0 90 non condensing GENERAL Input power requirements See rear panel for input voltage and f...

Page 13: ...ock absorbing material on all sides of the container Remove the tester from its container and place it on a test bench AC Line Voltage Requirements AC line voltage requirements for your Tester are not...

Page 14: ...11 Figure 2 Controls Indicators Connectors Model HT 3000P Front Panel...

Page 15: ...d the test will be terminated 5 Full Voltage LED If full voltage is successfully reached the Full Voltage LED will light and the high voltage duration timer starts 6 Hipot Fail LED Indicates failure o...

Page 16: ...13 Figure 3 Controls Indicators Connectors Model HT 3000P Rear Panel...

Page 17: ...ent of the High Voltage Ramp Time for this procedure 4 Test Time Adjustment Used to adjust high voltage test duration See Adjustment of the High Voltage Test Duration section for this procedure 5 Leak...

Page 18: ...15...

Page 19: ...osition 8 Verify that all test leads are disconnected from the HT 3000P 9 Push the red RESET button then the yellow TEST button 10 The tester should sound the buzzer The red Ground Open and red RESET...

Page 20: ...may light and in some instances the Ground OK LED may extinguish Passage of these tests indicates that the HT 3000P is functioning properly and that it is safe to use If the results of the performanc...

Page 21: ...ons Use this procedure if adjustment to a different ramp time within the range of 1 5 seconds is required 1 Defeat the Ground Check by turning the rear panel switch to the Off position 2 Connect the H...

Page 22: ...the rear panel turn the Test Time potentiometer As soon as the potentiometer starts turning the meter will display d and the value can be set in 1 second increments from 1 to 60 seconds 4 If tamperpro...

Page 23: ...e power switch to the I or ON position Push the RESET button The yellow TEST indicator should light indicating that the HT 3000P is ready to test 2 Connect the HTT 1 to the HT 3000P tester using the c...

Page 24: ...f time set in the Test Duration procedure If a breakdown of the insulation system between primary voltage and ground is detected the red Hipot Fail LED will light the buzzer will sound and the test wi...

Page 25: ...ssistance Phone 800 748 6224 Technical Assistance is available from Compliance West USA between the hours of 8 30 AM and 4 30 PM Pacific Time Compliance West USA 2120 Jimmy Durante Blvd Suite 118 Del...

Page 26: ...23...

Page 27: ...ad with a banana plug on one end are required to conduct the performance test The test equipment required for the calibration procedure is a DMM able to read true rms 0 2000 Vac 1 0 2800 Vdc 1 and a 3...

Page 28: ...the front panel and case with a mild solution of detergent and a damp sponge Clean dust from the PWB with clean dry low pressure 20 psi Calibration Procedure The Calibration Procedure should be perfo...

Page 29: ...r clip end to the 3 ohm resistor 3 Connect the banana plug end of the other lead to the round grounding jack of the DEVICE receptacle and the alligator clip end to the 3 ohm resistor 4 Turn the Ground...

Page 30: ...a test and using the 1000 1 voltage probe to check the meter at different voltages If the voltages are not within 2 at each voltage the voltage calibration must be performed again starting at step 1 a...

Reviews: