COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
HC6B048F3(C)
INDOOR COIL MODEL NO.
AHX60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1400
1600
1800
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
45.7
48.6
48.5
52.9
58.0
47.6
49.7
49.6
54.2
59.4
49.4
50.9
50.8
55.5
60.7
S.C.
45.7
42.2
36.3
35.9
29.9
47.6
45.2
38.3
37.9
30.9
49.4
48.1
40.3
39.9
32.0
K.W.
2.57
2.58
2.58
2.59
2.62
2.65
2.66
2.66
2.67
2.71
2.73
2.73
2.73
2.75
2.79
75
T.C.
44.1
46.4
46.3
50.6
55.4
45.8
47.4
47.4
51.7
56.6
47.6
48.4
48.4
52.9
57.8
S.C.
44.1
41.4
35.3
35.0
28.7
45.8
44.1
37.3
36.9
29.8
47.6
46.9
39.3
38.8
30.8
K.W.
2.90
2.91
2.91
2.92
2.95
2.98
2.98
2.98
3.00
3.04
3.06
3.06
3.06
3.08
3.12
85
T.C.
42.5
44.3
44.2
48.3
52.8
44.1
45.1
45.1
49.3
53.8
45.7
45.9
45.9
50.3
54.8
S.C.
42.5
40.5
34.3
34.0
27.5
44.1
43.0
36.3
35.9
28.6
45.7
45.6
38.3
37.8
29.6
K.W.
3.23
3.24
3.24
3.26
3.29
3.31
3.31
3.31
3.34
3.37
3.39
3.39
3.39
3.42
3.45
95
T.C.
40.9
42.1
42.1
45.9
50.2
42.4
42.7
42.8
46.8
51.0
43.9
43.4
43.5
47.7
51.9
S.C.
40.9
39.6
33.4
33.0
26.3
42.4
42.0
35.3
34.9
27.4
43.9
43.4
37.3
36.7
28.4
K.W.
3.56
3.56
3.56
3.59
3.62
3.64
3.64
3.64
3.67
3.70
3.73
3.72
3.72
3.75
3.79
105
T.C.
38.2
38.6
38.6
42.6
46.5
39.6
39.6
39.2
43.1
47.2
41.0
40.6
39.7
43.6
48.0
S.C.
38.2
37.7
31.8
31.6
24.8
39.6
39.6
33.8
33.4
25.9
41.0
40.6
35.8
35.2
27.0
K.W.
3.96
3.96
3.96
4.00
4.03
4.05
4.04
4.04
4.07
4.11
4.13
4.13
4.12
4.15
4.19
115
T.C.
35.6
35.1
35.0
39.3
42.8
36.8
36.4
35.5
39.4
43.4
38.0
37.7
36.0
39.6
44.1
S.C.
35.6
35.1
30.3
30.2
23.3
36.8
36.4
32.3
32.0
24.4
38.0
37.7
34.3
33.8
25.6
K.W.
4.36
4.36
4.36
4.40
4.44
4.45
4.45
4.44
4.48
4.52
4.54
4.54
4.52
4.55
4.60
125
T.C.
32.9
31.6
31.5
36.0
39.1
34.0
33.3
31.9
35.8
39.6
35.1
34.9
32.3
35.5
40.2
S.C.
32.9
31.6
28.8
28.8
21.8
34.0
33.3
30.8
30.6
22.9
35.1
34.9
32.3
32.3
24.1
K.W.
4.77
4.76
4.75
4.81
4.84
4.86
4.85
4.83
4.88
4.93
4.95
4.94
4.92
4.95
5.01
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC62
0.99
0.98
1.01
–
FC64
1.01
1.02
1.01
AHE60D
–
1.00
1.23
1.00
AHR60D
–
0.98
1.22
1.05
AHV60D
–
1.01
1.01
1.01
MV20D
FC/MC62D
1.00
1.00
0.96
MV20D
FC64
0.96
0.95
0.96
MX20D
FC/MC62D
0.99
0.99
0.94
MX20D
FC64
0.96
0.95
0.99
Furnace
Coil
T.C.
S.C.
KW
T*(8,L)V*C16
FC64
1.03
1.04
0.99
T*(8,L)V*C20
FC64
1.03
1.05
0.98
T*(8,L)X*C16
FC64
1.03
1.05
0.97
T*(8,L)X*C20
FC/MC62D
1.01
1.02
0.97
T*(8,L)X*C20
FC64
1.04
1.05
0.97
T*9(C,V)*C16
FC64
1.03
1.04
0.99
T*9X*C16
FC64
1.03
1.05
0.98
T*9X*C20
FC/MC62D
0.99
0.99
0.96
T*9X*C20
FC64
1.03
1.05
0.97
T*9X*D20
FC64
1.03
1.05
0.98
C*(8,L)C*C16
FC64
1.03
1.04
0.99
C*(8,L)C*C20
FC64
1.03
1.05
0.98
C*9C*C16
FC64
1.03
1.04
0.99