30
Johnson Controls Unitary Products
632152-CTG-E-0812
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
HIGH CFM
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
HC6B060F3(C)
INDOOR COIL MODEL NO.
AHX60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1730
1930
2130
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
56.5
59.8
59.9
65.4
70.1
58.4
60.9
60.8
66.6
71.7
60.4
62.0
61.7
67.8
73.3
S.C.
56.5
50.7
43.5
43.0
35.1
58.4
53.4
45.4
44.8
36.3
60.4
56.1
47.3
46.7
37.5
K.W.
3.50
3.54
3.54
3.62
3.71
3.60
3.64
3.63
3.71
3.81
3.71
3.73
3.73
3.80
3.92
75
T.C.
54.3
56.8
56.9
62.1
67.1
56.0
57.8
57.7
63.2
68.3
57.8
58.8
58.5
64.2
69.6
S.C.
54.3
49.5
42.2
41.6
33.7
56.0
52.1
44.1
43.5
34.8
57.8
54.8
45.9
45.4
35.9
K.W.
3.90
3.94
3.93
4.01
4.11
4.00
4.03
4.03
4.10
4.20
4.11
4.12
4.12
4.19
4.30
85
T.C.
52.0
53.8
53.9
58.9
64.0
53.6
54.7
54.7
59.7
64.9
55.2
55.5
55.4
60.6
65.8
S.C.
52.0
48.2
40.9
40.3
32.3
53.6
50.8
42.7
42.2
33.3
55.2
53.5
44.6
44.0
34.4
K.W.
4.30
4.33
4.33
4.40
4.50
4.40
4.42
4.42
4.50
4.59
4.50
4.51
4.51
4.59
4.69
95
T.C.
49.8
50.8
50.9
55.6
60.9
51.2
51.5
51.6
56.3
61.5
52.7
52.3
52.3
57.1
62.1
S.C.
49.8
46.9
39.5
39.0
30.9
51.2
49.6
41.4
40.8
31.9
52.7
52.2
43.3
42.6
32.8
K.W.
4.70
4.72
4.72
4.80
4.90
4.80
4.81
4.81
4.89
4.99
4.90
4.90
4.90
4.98
5.08
105
T.C.
46.7
47.1
47.1
51.5
56.3
48.0
48.0
47.7
52.2
56.9
49.3
49.0
48.3
52.9
57.4
S.C.
46.7
45.3
37.9
37.3
29.1
48.0
47.2
39.8
39.1
30.1
49.3
49.0
41.6
40.9
31.1
K.W.
5.22
5.23
5.23
5.32
5.41
5.32
5.33
5.32
5.41
5.50
5.43
5.42
5.41
5.50
5.59
115
T.C.
43.6
43.3
43.2
47.5
51.7
44.7
44.6
43.8
48.0
52.2
45.9
45.8
44.3
48.6
52.7
S.C.
43.6
43.3
36.2
35.7
27.4
44.7
44.6
38.1
37.5
28.3
45.9
45.8
40.0
39.2
29.3
K.W.
5.75
5.74
5.74
5.84
5.92
5.85
5.85
5.83
5.92
6.01
5.95
5.95
5.92
6.01
6.10
125
T.C.
40.6
39.6
39.4
43.4
47.0
41.5
41.1
39.9
43.9
47.5
42.5
42.5
40.4
44.4
48.0
S.C.
40.6
39.6
34.6
34.0
25.6
41.5
41.1
36.5
35.8
26.6
42.5
42.5
38.4
37.6
27.5
K.W.
6.27
6.25
6.25
6.36
6.43
6.38
6.36
6.34
6.44
6.52
6.48
6.48
6.42
6.52
6.61
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC62D
0.99
0.97
1.02
–
FC64
1.02
1.02
1.03
AHE60D
–
1.00
0.99
1.00
AHV60D
–
0.98
0.94
0.98
MV20D
FC/MC62D
1.04
0.98
0.98
MV20D
FC64
1.07
1.02
0.98
MX20D
FC/MC62D
1.00
0.99
0.98
MX20D
FC64
1.04
1.03
0.98
Furnace
Coil
T.C.
S.C.
KW
T*(8,L)V*C16
FC/MC62D
1.03
0.98
1.00
T*(8,L)V*C16
FC64
1.06
1.00
1.00
T*(8,L)V*C20
FC/MC62D
1.03
0.98
0.99
T*(8,L)V*C20
FC64
1.06
1.02
0.99
T*(8,L)X*C16
FC/MC62D
1.03
0.98
0.98
T*(8,L)X*C16
FC64
1.07
1.02
0.99
T*(8,L)X*C20
FC64
1.07
1.02
0.99
T*9(C,V)*C16
FC/MC62D
1.03
0.97
1.00
T*9(C,V)*C16
FC64
1.06
1.00
1.01
T*9(C,V)*C20
FC/MC62D
1.02
0.97
1.01
T*9(C,V)*C20
FC64
1.06
1.00
1.02
T*9(C,V)*D20
FC/MC62D
1.03
0.97
1.01
T*9(C,V)*D20
FC64
1.06
1.00
1.01
T*9X*C16
FC/MC62D
1.03
0.98
0.99
T*9X*C16
FC64
1.06
1.02
0.99
T*9X*C20
FC/MC62D
1.03
0.97
0.98
T*9X*C20
FC64
1.06
1.00
0.99
T*9X*D20
FC/MC62D
1.02
0.97
0.98
T*9X*D20
FC64
1.06
1.00
0.99
C*(8,L)C*C16
FC/MC62D
1.03
0.98
1.00
C*(8,L)C*C16
FC64
1.06
1.00
1.00
C*(8,L)C*C20
FC/MC62D
1.03
0.98
0.99
C*(8,L)C*C20
FC64
1.06
1.02
0.99
C*9C*C16
FC/MC62D
1.03
0.97
1.00
C*9C*C16
FC64
1.06
1.00
1.01
C*9C*C20
FC/MC62D
1.02
0.97
1.01
C*9C*C20
FC64
1.06
1.00
1.02
C*9C*D20
FC/MC62D
1.03
0.97
1.01
C*9C*D20
FC64
1.06
1.00
1.01
Furnace
Coil
T.C.
S.C.
KW