22
Johnson Controls Unitary Products
632152-CTG-E-0812
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
HC6B024F3(C)
INDOOR COIL MODEL NO.
AHX30
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
635
835
1035
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
21.7
24.2
24.1
26.2
28.4
23.9
25.3
25.2
27.3
29.5
26.1
26.4
26.3
28.5
30.5
S.C.
21.7
20.6
17.8
17.8
14.8
23.9
23.6
19.7
19.6
15.7
26.1
26.4
21.7
21.4
16.6
K.W.
1.19
1.19
1.19
1.19
1.19
1.26
1.26
1.27
1.27
1.27
1.34
1.34
1.34
1.35
1.35
75
T.C.
21.2
23.2
23.1
25.1
27.2
23.1
24.2
24.0
26.1
28.2
25.1
25.1
25.0
27.2
29.3
S.C.
21.2
20.1
17.3
17.3
14.4
23.1
22.8
19.2
19.1
15.3
25.1
25.1
21.2
20.9
16.2
K.W.
1.36
1.36
1.36
1.36
1.37
1.43
1.44
1.44
1.44
1.45
1.51
1.51
1.51
1.52
1.53
85
T.C.
20.6
22.1
22.1
24.0
26.0
22.3
23.0
22.9
24.9
27.0
24.1
23.9
23.8
25.9
28.0
S.C.
20.6
19.6
16.8
16.8
13.9
22.3
22.0
18.8
18.6
14.9
24.1
23.9
20.7
20.4
15.8
K.W.
1.52
1.53
1.53
1.54
1.55
1.61
1.61
1.61
1.62
1.63
1.69
1.69
1.69
1.70
1.71
95
T.C.
20.0
21.1
21.0
23.0
24.8
21.5
21.9
21.8
23.8
25.7
23.1
22.6
22.5
24.5
26.7
S.C.
20.0
19.2
16.4
16.3
13.4
21.5
21.3
18.3
18.1
14.4
23.1
22.6
20.2
19.8
15.4
K.W.
1.69
1.70
1.70
1.71
1.72
1.78
1.78
1.78
1.79
1.81
1.86
1.86
1.86
1.87
1.89
105
T.C.
19.1
19.8
19.8
21.6
23.4
20.5
20.7
20.4
22.3
24.1
21.8
21.6
21.1
23.0
24.9
S.C.
19.1
18.6
15.8
15.7
12.8
20.5
20.5
17.7
17.5
13.7
21.8
21.6
19.6
19.3
14.7
K.W.
1.90
1.90
1.90
1.92
1.93
1.98
1.99
1.98
2.00
2.01
2.07
2.07
2.06
2.08
2.10
115
T.C.
18.1
18.6
18.6
20.3
21.9
19.4
19.6
19.1
20.8
22.5
20.6
20.6
19.6
21.4
23.1
S.C.
18.1
18.1
15.3
15.0
12.2
19.4
19.6
17.1
16.9
13.1
20.6
20.6
19.0
18.7
13.9
K.W.
2.11
2.11
2.11
2.12
2.14
2.19
2.19
2.19
2.20
2.22
2.28
2.28
2.27
2.29
2.30
125
T.C.
17.2
17.3
17.4
18.9
20.5
18.3
18.5
17.8
19.4
20.9
19.4
19.6
18.2
19.8
21.4
S.C.
17.2
17.3
14.8
14.4
11.6
18.3
18.5
16.6
16.3
12.4
19.4
19.6
18.2
18.2
13.2
K.W.
2.32
2.31
2.32
2.33
2.34
2.40
2.40
2.39
2.41
2.43
2.49
2.49
2.47
2.49
2.51
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC32
0.97
0.95
1.08
–
FC/MC/PC35
0.97
0.95
1.08
–
FC/MC/PC37
0.98
0.97
1.08
–
FC/MC/PC43
0.98
0.97
1.08
AHE24B
–
1.00
0.98
0.99
AHE30B
–
1.00
0.98
0.99
AHR24B
–
0.97
0.93
1.03
AHV24B
–
0.97
0.93
0.97
AHV30B
–
0.99
0.96
0.99
AHV36C
–
1.00
0.97
0.97
AV*36
–
0.99
0.96
0.96
MV12B
FC/MC35B
1.00
0.97
0.98
MV12B
FC/MC43B
1.01
0.99
0.98
MX12B
FC/MC35B
1.00
0.98
0.95
MX12B
FC/MC43B
0.99
0.96
0.96