Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature
Continued on next page.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
HC6B036F3(C)
INDOOR COIL MODEL NO.
AHX42
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1000
1200
1400
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
34.1
36.2
36.4
39.6
43.0
36.1
37.4
37.5
40.8
44.1
38.1
38.5
38.5
42.0
45.3
S.C.
34.1
31.2
26.9
26.6
21.7
36.1
34.5
28.9
28.5
22.8
38.1
37.8
30.9
30.3
23.9
K.W.
1.93
1.93
1.94
1.94
1.95
2.01
2.02
2.02
2.03
2.04
2.10
2.10
2.10
2.13
2.12
75
T.C.
32.9
34.7
34.8
38.0
41.2
34.8
35.7
35.7
38.9
42.2
36.6
36.6
36.7
39.9
43.3
S.C.
32.9
30.5
26.1
25.8
21.0
34.8
33.4
28.1
27.7
22.1
36.6
36.3
30.1
29.6
23.1
K.W.
2.20
2.20
2.20
2.21
2.23
2.29
2.29
2.29
2.30
2.32
2.37
2.37
2.37
2.39
2.41
85
T.C.
31.8
33.1
33.2
36.3
39.4
33.5
34.0
34.0
37.1
40.3
35.2
34.8
34.8
37.8
41.2
S.C.
31.8
29.8
25.4
25.1
20.3
33.5
32.3
27.4
27.0
21.3
35.2
34.7
29.4
28.9
22.4
K.W.
2.47
2.47
2.47
2.49
2.51
2.56
2.56
2.56
2.57
2.60
2.65
2.64
2.65
2.65
2.69
95
T.C.
30.6
31.5
31.6
34.6
37.6
32.1
32.3
32.3
35.2
38.4
33.7
33.0
33.0
35.8
39.2
S.C.
30.6
29.1
24.6
24.3
19.6
32.1
31.1
26.6
26.2
20.6
33.7
33.0
28.7
28.2
21.6
K.W.
2.74
2.74
2.74
2.77
2.79
2.83
2.83
2.83
2.84
2.89
2.92
2.91
2.92
2.90
2.98
105
T.C.
29.0
29.3
29.6
32.4
35.3
30.4
30.4
30.1
32.9
35.9
31.7
31.4
30.6
33.4
36.5
S.C.
29.0
28.2
23.7
23.4
18.6
30.4
29.9
25.7
25.3
19.7
31.7
31.4
27.7
27.2
20.7
K.W.
3.06
3.05
3.07
3.05
3.07
3.13
3.12
3.15
3.12
3.16
3.20
3.20
3.23
3.20
3.25
115
T.C.
27.4
27.2
27.6
30.2
33.0
28.6
28.5
27.9
30.6
33.4
29.8
29.8
28.2
31.0
33.9
S.C.
27.4
27.2
22.8
22.5
17.6
28.6
28.5
24.8
24.4
18.7
29.8
29.8
26.7
26.3
19.7
K.W.
3.38
3.35
3.40
3.32
3.34
3.43
3.42
3.47
3.41
3.43
3.49
3.49
3.54
3.50
3.52
125
T.C.
25.9
25.0
25.6
28.0
30.7
26.9
26.6
25.7
28.4
30.9
27.9
28.2
25.8
28.7
31.2
S.C.
25.9
25.0
21.9
21.6
16.7
26.9
26.6
23.8
23.5
17.7
27.9
28.2
25.8
25.4
18.8
K.W.
3.70
3.65
3.73
3.60
3.62
3.73
3.71
3.79
3.70
3.70
3.77
3.77
3.85
3.79
3.79
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC48
0.97
0.97
1.00
–
FC/MC/PC60
0.98
0.98
1.01
–
UC48
0.98
0.98
1.00
–
UC60
0.97
0.96
1.00
AHE42D
–
0.99
1.08
0.92
AHE48D
–
0.99
1.08
0.91
AHR42C
–
0.98
1.08
1.00
AHV42D
–
0.99
1.08
0.92
AHV48D
–
0.99
1.06
0.91
AV*48
–
1.01
1.11
0.92
MV12D
FC/MC48D
1.00
1.08
0.91
MV12D
FC/MC60D
0.99
1.07
0.93
MV16C
FC/MC48C
0.99
1.08
0.93
MX12D
FC/MC48D
0.99
1.08
0.93
MX12D
FC/MC60D
1.01
1.13
0.93
MX16C
FC/MC48C
1.00
1.08
0.91