PROCEDURES:
1. Unit factory charge listed on the unit nameplate includes refrigerant for the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.
2. Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.
4. For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit +
charge adder for line set.
System Charge for Various Matched Systems
Outdoor Unit
HC6B024F3(C) HC6B030F3(C) HC6B036F3(C) HC6B042F4(C) HC6B048F3(C) HC6B060F3(C)
Required TXV
1,2
4N1
4H1
4H1
4J1
4J1
4K1
Indoor Unit
3
,
4
,
5
Additional Charge, Oz
AHE24B
TXV + 0
–
–
–
–
–
AHE30B
TXV + 0
–
–
–
–
–
AHE36C
–
TXV + 0
–
–
–
–
AHE42D
–
–
TXV + 0
–
–
–
AHE48D
–
–
TXV + 20
TXV + 0
–
–
AHE60D
–
–
–
TXV + 5
TXV + 0
TXV + 0
AHR24B
TXV + 0
–
–
–
–
–
AHR36B
–
TXV + 0
–
–
–
–
AHR42C
–
–
TXV + 0
–
–
–
AHR60D
–
–
–
TXV + 0
TXV + 0
–
AHV24B
TXV + 0
–
–
–
–
–
AHV30B
TXV + 0
–
–
–
–
–
AHV36C
TXV + 12
TXV + 0
–
–
–
–
AHV42D
–
–
TXV + 0
–
–
–
AHV48D
–
–
TXV + 20
TXV + 0
–
–
AHV60D
–
–
–
TXV + 5
TXV + 0
TXV + 0
AV*36
TXV + 12
TXV + 0
–
–
–
–
AV*48
–
–
TXV + 20
TXV + 0
–
–
FC/MC/PC32
TXV + 0
–
–
–
–
–
FC/MC/PC35
TXV + 0
–
–
–
–
–
FC/MC/PC37
TXV + 12
TXV + 0
–
–
–
–
FC/MC/PC43
TXV + 12
TXV + 0
–
–
–
–
FC/MC/PC48
–
–
TXV + 0
–
–
–
FC/MC/PC60
–
–
TXV + 20
TXV + 0
–
–
FC/PC62
–
–
–
TXV + 5
TXV + 0
TXV + 0
FC64
–
–
–
–
TXV + 8
TXV + 8
UC48
–
–
TXV + 15
–
–
–
UC60
–
–
TXV + 31
TXV + 2
–
–
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. A TXV kit must be used with these indoor units to obtain system performance.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.
4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
5. Refer to Cooling and Heating Performance Data tables for actual performance for specified system matches.
Note:
If a TXV is factory installed on the coil, it must be replaced with the listed TXV.