Johnson Controls Unitary Products
27
632152-CTG-E-0812
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
Continued on next page.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
HC6B042F4(C)
INDOOR COIL MODEL NO.
AHE60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1185
1385
1585
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
39.3
41.5
41.5
45.3
49.4
41.1
42.5
42.5
46.4
50.6
42.9
43.5
43.5
47.5
51.8
S.C.
37.4
34.6
29.5
29.1
23.2
39.1
38.0
31.5
31.1
24.4
40.7
41.4
33.5
33.1
25.6
K.W.
2.22
2.22
2.23
2.26
2.31
2.31
2.30
2.30
2.36
2.39
2.40
2.37
2.38
2.45
2.47
75
T.C.
37.9
39.6
39.6
43.4
47.3
39.6
40.5
40.5
44.3
48.4
41.3
41.4
41.4
45.3
49.4
S.C.
36.1
33.8
28.7
28.4
22.5
37.7
36.6
30.7
30.3
23.6
39.3
39.3
32.7
32.2
24.8
K.W.
2.52
2.53
2.53
2.55
2.56
2.60
2.61
2.61
2.62
2.65
2.68
2.69
2.69
2.70
2.73
85
T.C.
36.5
37.7
37.8
41.5
45.3
38.2
38.5
38.5
42.3
46.2
39.8
39.3
39.3
43.0
47.0
S.C.
34.7
33.1
27.9
27.6
21.8
36.3
35.2
29.9
29.5
22.9
37.8
37.3
31.9
31.4
24.0
K.W.
2.83
2.84
2.84
2.83
2.82
2.90
2.92
2.92
2.89
2.90
2.97
3.00
3.00
2.95
2.98
95
T.C.
35.1
35.9
35.9
39.6
43.3
36.7
36.5
36.6
40.2
44.0
38.2
37.1
37.3
40.8
44.6
S.C.
33.4
32.3
27.1
26.8
21.1
34.9
33.8
29.1
28.7
22.1
36.3
35.3
31.0
30.5
23.1
K.W.
3.13
3.15
3.14
3.11
3.08
3.19
3.23
3.22
3.16
3.16
3.25
3.31
3.31
3.21
3.24
105
T.C.
33.4
33.6
33.6
37.0
40.4
34.8
34.6
34.2
37.5
41.1
36.1
35.6
34.8
38.1
41.7
S.C.
31.8
31.0
26.1
25.8
20.1
33.1
32.4
28.1
27.7
21.1
34.3
33.8
30.0
29.5
22.2
K.W.
3.44
3.45
3.44
3.45
3.45
3.51
3.53
3.52
3.51
3.53
3.59
3.61
3.61
3.57
3.61
115
T.C.
31.7
31.3
31.4
34.4
37.6
32.9
32.7
31.8
34.9
38.2
34.0
34.0
32.3
35.4
38.7
S.C.
30.1
29.8
25.2
24.8
19.1
31.2
31.0
27.1
26.7
20.1
32.4
32.3
29.0
28.5
21.2
K.W.
3.75
3.74
3.74
3.78
3.82
3.84
3.83
3.82
3.86
3.90
3.92
3.92
3.90
3.94
3.98
125
T.C.
30.0
29.1
29.2
31.8
34.8
31.0
30.7
29.5
32.3
35.3
31.9
32.4
29.8
32.7
35.8
S.C.
28.5
28.5
24.3
23.8
18.1
29.4
29.7
26.1
25.7
19.1
30.4
30.8
28.0
27.5
20.2
K.W.
4.06
4.04
4.04
4.12
4.18
4.16
4.14
4.12
4.21
4.27
4.26
4.23
4.20
4.31
4.35
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Air Handler
Coil
T.C.
S.C.
KW
–
FC/MC/PC60
0.96
0.94
1.06
–
FC/MC62
0.97
0.98
1.09
–
UC60
0.96
0.95
1.06
AHE48D
–
0.98
0.98
0.98
AHE60D
–
1.00
1.00
1.00
AHR60D
–
0.97
0.98
1.07
AHV48D
–
0.98
0.96
0.98
AHV60D
–
0.98
1.00
1.02
AV*48
–
1.00
1.00
0.98
MV16C
FC60C
0.98
0.98
0.99
MV20D
FC/MC60D
1.00
1.02
0.99
MV20D
FC/MC62D
1.00
1.00
1.03
MX16C
FC60C
0.98
0.99
0.97
MX20D
FC/MC60D
1.01
1.03
0.98
MX20D
FC/MC62D
1.01
1.05
1.01