Operator's Manual: Models CB-3500 & CB-5000
10-2
Main power ON sending power to centrifugal switch and both high limit switches.
Burner cable plugged in.
Green indicator light ON.
Preheater thermostat activates 400 w
att block
heater element and heats the block t
o 140 °F
.
INITIAL
ST
AR
T-UP
Preheater thermostat cycles 400 wat
t block
heater element and maintains 140 °F
block
temperature.
NORMAL
BURNER OPERA
TION
When block temperature reaches 12
0 °F , the
F120 proving switch closes and send
s power
to the oil primary control.
F120 proving switch remains closed a
nd oil
primary control has power
.
Oil primary control checks for 2000+ ohms from cad cell indicating dark in the combustion chamber (NO FLAME)
BURNER PRE-IGNITION SEQUENCE
Oil primary control relay closes.
Burner ignition sequence begins.
BURNER IGNITION SEQUENCE
14,000 volt igniter starts, providing interrupted ignition (approx. 45 sec. of spark at electrode gap)
Air solenoid opens.
INITIAL
ST
AR
T-UP
Air regulator adjusted to proper psi of air pressure.
Air sensing switch closes as it receives more than 10 psi of air pressure.
Pump circuit starts oil pump.
Yellow indicator light ON.
Pump circuit opens oil solenoid.
Air sensing switch receives power from centrifugal switch.
INITIAL
ST
AR
T-UP
Combustion air band adjusted for proper combustion air
.
Centrifugal switch closes and sends power to air sensing switch.
Burner motor starts and reaches full rpm.
Burner ignites.
Oil primary control receives <500 ohm signal from cad cell indicating proper ignition.
Burner continues to run until the wall thermostat is satisfied.
FURNACE HEA
TING SEQUENCE
Blower switch on combustion chamber senses temperature rise as the burner fires.
Blower switch senses ON temperature (180 °F) and Blower switch closes.
Blower switch sends power to motor (CB-1750) or relay (CB-2500 / 3250), and blower starts.
W
all thermostat is
satisfied
and T
circuit opens.
Primary control relay opens and the burner shuts of
f.
Blower continues to run to drive latent heat from the heat exchanger
.
Blower switch senses OFF temperature (160 °F) and Blower switch opens.
Blower stops running.
FURNACE COOL
DOWN SEQUENCE
W
arm air delivered
to heated area.
Hour meter starts.
W
all thermostat calls for heat and
closes 24V thermostat.
FLOW CHART
CB-3250
230 V / 60 Hz
I88792-B
FLOW CHART
CB-1750/2500/3250
115 V / 60 Hz
Summary of Contents for CB-3500 series
Page 2: ......
Page 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Page 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Page 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Page 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Page 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Page 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Page 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Page 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Page 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...