Operator's Manual: Models CB-3500 & CB-5000
3-8
Air Flow (CFM) and Static Pressure (SP) Specifications
Determining the Air Discharge Configuration
The CB-3500 and CB-5000 furnaces may be configured for use as EITHER a Unit Heater or a Central Furnace as
described below.
(1)
Unit Heater
Furnace with blower for FREE AIR applications.
HOT AIR DISCHARGE: Louver assembly (components supplied)
NOTE:
If the peak of your shop roof/ceiling is 14 feet or higher, install
industrial-size ceiling fans to aid in efficient, even heat distribution. A minimum
of one Clean Burn 56" Blade Industrial Ceiling Fan (C.B. part# 70003) or
equivalent is recommended for each 2000 square feet of shop space.
Be sure to adhere to the specified clearances as stated in Section 4 of this
manual.
(2)
Central Furnace
Furnace with blower for DUCTING applications from .25 to .40 static
pressure.*
HOT AIR DISCHARGE: Ductwork
(Refer to the following chart for the
proper air discharge/ducting specifications; installation to be accomplished by
HVAC professionals ONLY.)
Be sure to adhere to the specified clearances as stated in Section 4 of this
manual.
Installing the Hot Air Discharge Components
*ATTENTION:
A qualified electrician must check the blower motor amperage during operation of the furnace to ensure
that motor amperage does not exceed 85% of the maximum amperage on the motor label. DO NOT operate the blower motor
above 85% of maximum amperage or motor damage may occur.
Air Discharge Louvers Mounted on Furnace
(Fully Open - Ductwork Installed Over Top)*
0.25 Inches of W.C.**
0.25 Inches of W.C.**
Air Discharge Louvers Mounted on Furnace
(Fully Open - Ductwork Installed Over Top)*
Air Discharge Louvers
Mounted on Furnace
Duct Free**
5500 CFM
CB-5000
CB-3500
C77003
4200 CFM
Duct Free**
Air Discharge Louvers
Mounted on Furnace
Air Discharge Louvers Removed
Ductwork Installed on Furnace
0.40 Inches of W.C.**
5200 CFM
5100 CFM
0.40 Inches of W.C.**
Air Discharge Louvers Removed
Ductwork Installed on Furnace
3900 CFM
4000 CFM
Summary of Contents for CB-3500 series
Page 2: ......
Page 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Page 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Page 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Page 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Page 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Page 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Page 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Page 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Page 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...