Operator's Manual: Models CB-3500 & CB-5000
4-8
Oil Tank Installation Specifications (continued)
Figure 4F - Typical Metering Pump Installation with Inside Tank
Installing the Tank Vent and Emergency Vent
Some codes require that you install a tank vent (to the outside) and an emergency vent for your tank as shown in
Figure 4F.
Tank Vent Kits
are available from Clean Burn; contact your local Clean Burn dealer to order. Be sure
to check your local codes for any additional tank installation requirements, and adhere to the following installa-
tion guidelines:
• Install a length of minimum 2" steel pipe (user-supplied) terminating outside with a proper
vent cap as shown in Figure 4F. Consult local codes for information and requirements
concerning the proper venting of oil storage tanks.
• Install an emergency vent as shown in Figure 4F. Contact your tank manufacturer for
information concerning the proper emergency vent for your tank.
PUMP
SUCTION LINE
ASSEMBLY
I88669-H
EMERGENCY
VENT
MUSHROOM
CAP VENT
ROT
ATIO
N
INLE
T
GAUG
E
SCREEN
FILTER
42366
OIL ST
ORA
GE T
ANK
VALVE
CHECK
(USER SUPPLIED)
STEEL PIPE
FUNNEL WITH
BALL VALVE
CLEAN-OUT
(TANK DRAIN)
TANK VENT KITS AVAILABLE FROM CLEAN BURN
Example Oil Tank Install Diagram
REL
IEF
PRESSURE
LINE
PRESSURE
RELIEF OIL
LINE BACK TO
THE TANK
Summary of Contents for CB-3500 series
Page 2: ......
Page 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Page 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Page 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Page 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Page 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Page 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Page 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Page 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Page 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...