Operator's Manual: Models CB-3500 & CB-5000
4-19
Installing the Interior Stack
WARNING:
Single wall stack components may be used
only
for those portions of the stack
which are located inside your building and away from any fire/burn hazards.
1.
Install the single wall stack with proper clearances from combustibles. Also ensure that the stack
is located a safe distance from all shop personnel.
2.
Install an elbow at the junction of the horizontal and vertical stack components to allow for easy cleaning
of the stack.
ATTENTION:
Avoid additional 90-degree turns in the stack. Each additional 90-degree turn
slows down stack gases, creates back-pressure, and results in repeated burner shutdown and
unnecessary service calls. All other turns in the stack should be at a 45-degree (or smaller) angle.
NOTE:
IMPORTANT for Canadian Installations
- Local codes may require the installation of
a clean-out tee.
Figure 4L - Installation of "Class A" Stack Through Roof/Ceiling
SINGLE W
ALL
ST
ACK
"CLASS A" KIT FOR
INSTALLING
"CLASS A" STACK
THROUGH CEILING
I88805-C
WARNING! ENSURE PROPER
CLEARANCES BETWEEN STACK
COMPONENTS AND COMBUSTIBLES
PER ALL APPLICABLE CODES.
WARNING! BE SURE TO INSTALL
THE PROPER ROOF SUPPORT SYSTEM
TO SAFELY SUPPORT THE STACK
WATERTIGHT ROOF FLASHING:
CLEAN BURN RECOMMENDS
"DEKTITE" FLASHING FOR A
WATERTIGHT SEAL
'CLASS A
' ST
ACK C
OMPONENT
S
INSULA
TED ST
ACK
WITH A ST
AINLESS STEEL LINER
BAROMETRIC DAMPER MUST
BE INSTALLED SO IT IS FACING
AWAY FROM THE FAN TO
PREVENT EXHAUST GASES
FROM BEING SUCKED OUT
OF THE DAMPER OPENING
1/4" HOLE FOR
SETTING DRAFT.
ADJUST
BAROMETRIC
DAMPER FOR
-.04 W.C. DRAFT
AT BREECH
SINGLE W
ALL
ST
ACK
MIN. 24 GA
UGE
AIR OIL
WEIGHT
TURN
FOR MORE DRAFT
NOTE: THE LAST STACK SECTION SHALL EXTEND AT
LEAST 3 FEET (90 CM) HIGHER THAN ANY RIDGE,
PARAPET, WALL, OR ROOF STRUCTURE WITHIN 10
FEET (3 M) OF IT.
"CLASS A" STACK CAP
NON-RESTRICTIVE TYPE TO ALLOW
FREE FLOW OF THE STACK GASES
3 FT
. (90 cm)
10 FT. (3 M)
10 FT
. (3 M) MINIMUM
VER
TIC
AL ST
ACK HEIGHT
TO M
AINT
AIN PR
OPER DR
AFT OVERFIRE
Summary of Contents for CB-3500 series
Page 2: ......
Page 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Page 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Page 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Page 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Page 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Page 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Page 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Page 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Page 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...