Operator's Manual: Models CB-3500 & CB-5000
10-5
PROBLEM
POSSIBLE CAUSE(S)
POSSIBLE ACTION(S)
Burner ignites and Burner shuts off
on reset sometime later during the
day or night.
1. There is air in the fuel supply.
2. The primary control is not
receiving the proper ohm signal
from the cad cell.
3. There is insufficient air pressure.
4. The heater block is cold.
5. The electrodes are fouled.
1. Prime the pump. If the pump
will not prime or there is air in
the oil stream from the pump
bleeder, follow the steps in the next
problem (“Pump will not prime.”)
2. Check for proper ohm signal.
Follow the procedures in the
previous problem (top, page 10-4)
3. Follow the instructions in Section
5 to adjust the air regulator for
proper air pressure. DO NOT turn
the air compressor off while the
furnace is operating. If you turn
the air compressor off at night,
turn the wall thermostat to OFF so
the burner will not run.
4. DO NOT shut off power to the
furnace overnight, or the heater
block will cool down, and the
burner will not re-start the next
morning. To turn the furnace “off”
overnight, turn the wall thermostat
to OFF. The heater block will stay
hot.
5. If oil residues have built up on
the electrodes and retention head,
follow the instructions in Section 8
to check for proper draft overfire.
Clean the electrodes and retention
head as shown in Appendix A.
Summary of Contents for CB-3500 series
Page 2: ......
Page 18: ...Operator s Manual Models CB 3500 CB 5000 1 10 ...
Page 36: ...Operator s Manual Models CB 3500 CB 5000 3 16 ...
Page 68: ...Operator s Manual Models CB 3500 CB 5000 5 6 ...
Page 74: ...Operator s Manual Models CB 3500 CB 5000 6 6 ...
Page 94: ...Operator s Manual Models CB 3500 CB 5000 9 10 ...
Page 102: ...Operator s Manual Models CB 3500 CB 5000 10 8 ...
Page 107: ...Operator s Manual Models CB 3500 CB 5000 A 5 ...
Page 126: ...Operator s Manual Models CB 3500 CB 5000 A 24 ...
Page 134: ...Operator s Manual Models CB 3500 CB 5000 C 2 ...