• # 2 Phillips Dynamometric screwdriver
• ANSI—Six #12-24 x ¾ pan-head Phillips mounting screws
• ETSI—Six M6 mounting screws
Tools/Equipment
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves
Prerequisite Procedures
As needed
Required/As Needed
Onsite
Onsite/Remote
None
Security Level
The ONS 15454 M6 requires a minimum of six RU of vertical rack space. To ensure that the mounting is
secure, use two to three M6 mounting screws on each side of the shelf. A shelf should be mounted at the
bottom of the rack if it is the only unit in the rack.
Note
Procedure
Step 1
Verify that the proper fuse and alarm panel has been installed in the top mounting space. If a fuse and alarm
panel is not present, you must install one according to manufacturer instructions:
• For a DC power supply, the fuse rating must not exceed 40A.
• For an AC power supply, the fuse rating must not exceed 10A, 15A, or 20A. For North America, the
branch circuit protection must be rated 20A. The overcurrent/short circuit protection must be in accordance
with local and national electrical codes.
Step 2
Ensure that the shelf is mounted on the appropriate rack equipment:
• 23-inches (584.2 mm) or 19-inches (482.6 mm) for ANSI racks. The recommended 19-inch ANSI rack
for the ONS 15454 M6 shelf is shown in
.
• 600 x 600-mm (23.6 x 23.6-inch) or 600 x 300-mm (23.6 x 11.8-inch) for ETSI racks.
Diagram 1 of
Figure 42: Mounting an ONS 15454 M6 on a Rack, on page 47
shows the ONS 15454 M6 shelf
mounted on an ANSI rack in the middle position using 19-inch mounting brackets.
Diagram 2 of
Figure 42: Mounting an ONS 15454 M6 on a Rack, on page 47
shows the ONS 15454 M6 shelf
mounted on an ETSI rack in the front position.
Installing the ONS 15454 M6 Shelf
46
Installing the ONS 15454 M6 Shelf
DLP-G566 Mount the ONS 15454 M6 Shelf on a Rack (One Person)