PID
Cable
15454-M-CBL-LARG=
AC power cable - ARG left exit
15454-M-CBL-RARG=
AC power cable - ARG right exit
15454-M-CBL-LAUS=
AC power cable - AUS left exit
15454-M-CBL-RAUS=
AC power cable - AUS right exit
15454-M-CBL-L-UK=
AC power cable - UK left exit
15454-M-CBL-R-UK=
AC power cable - UK right exit
15454-M-CBL-LKOR=
AC power cable - KOR left exit
15454-M-CBL-RKOR=
AC power cable - KOR right exit
15454-M-ACCBL-L=
AC power cable ANSI 110VAC left exit
15454-M-ACCBL-R=
AC power cable ANSI 110VAC right exit
15454-M-ACCBL-L2=
AC power cable ANSI 220VAC left exit
15454-M-ACCBL-R2=
AC power cable ANSI 220VAC right exit
15454-M-ACL6-L=
AC power cable for data center left exit
15454-M-ACL6-R=
AC power cable for data center right exit
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)
This task connects DC power to the ONS 15454 M6 (ANSI Only).
Purpose
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Wire wrapper
• Wire cutters
• Wire strippers
• Crimp tool
• Open-end wrench or hex tube screw driver
• Fuse panel
• Power cable (from fuse and alarm panel to assembly), #8 AWG, copper
conductors, 194 degrees F (90 degrees C)
• Ground cable #6 AWG stranded
• Listed pressure dual-holes lugs suitable for #8 AWG copper conductors
Tools/Equipment
Installing the ONS 15454 M6 Shelf
107
Installing the ONS 15454 M6 Shelf
DLP-G572 Connect Office Power (DC) to the ONS 15454 M6 Shelf (ANSI Only)