E-35
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
OL-23069-07
Appendix E Repacking the Cisco Nexus 7000 Series Switch for Shipment
Repacking the System Components
d.
With one hand on the handle of the power supply unit, pull the unit partially out of the chassis.
e.
Place your other hand underneath the power supply unit to support the unit, and then pull the unit
fully out of the chassis.
f.
Place the power supply unit in an ESD packing bag and insert the bagged power supply unit in one
of the larger slots in the packing box (see Callout 3 in
Figure E-19
).
Note
For easier handling of a multi-unit box, arrange the power supply units so their weight is
balanced in the box. If you are packing only one unit, place it in the middle of the box. If
you are packing two units, place them in the large slots at each end of the box. If you are
packing three units, place one in the middle of the box and the other two in slots at either
end of the box. Always leave empty slots between power supply units so that you can pack
their cables.
g.
Put the DC power supply unit in an ESD bag and place the filler box in the cutout portion of the
power supply unit (see Callout 3 in
Figure E-19
).
h.
Insert the back end of the power supply unit and filler box into a foam block (see Callout 4 in
Figure E-19
).
i.
Expand the other foam block by pulling its two sides apart, and fit the block around the front of the
power supply unit before bringing the two sides together again (see Callout 5 in
Figure E-19
).
j.
Place the power supply unit and its foam blocks in the box (see Callout 6 in
Figure E-19
).
k.
Fold the narrow flaps over the power supply unit (see Callout 7 in
Figure E-19
).
l.
Fold the wide flaps over the narrow flaps (see Callout 8 in
Figure E-19
).
m.
Tape the wide flaps together and to the box with packing tape (see Callout 8 in
Figure E-19
).
Step 6
Disconnect the switch from the console and the network as follows:
a.
On each supervisor module, disconnect the cables connected to the Console, Com/AUX,
Management, and CMP Management ports.
b.
Disconnect all of the cables from each of the I/O modules.
Step 7
Disconnect the one or two chassis grounding connections as follows:
a.
Unscrew the two M4 screws that hold each ground lug to the chassis. For the locations of the two
grounding pads on the Cisco Nexus 7010 switch, see
Figure 4-6 on page 4-13
and
Figure 4-7 on
page 4-14
.
b.
Place the screws in the accessory kit.
Step 8
Disconnect the switch from the network as follows:
a.
Disconnect the cables that attach the Management and CMP processors on each supervisor module
to a console.
b.
Disconnect all of the I/O cables from the I/O modules.
Step 9
If the chassis includes the optional front door and air-intake frame, remove them as follows:
a.
Open the door by pulling one of its latch handles out until it clicks (the handle clicks when you pull
it out about 30 degrees) and rotate the door away from the chassis (see
Figure E-20
).
Summary of Contents for Nexus 7004
Page 12: ...Contents xii Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...
Page 19: ... xix Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...
Page 22: ... xxii Cisco Nexus 7000 Series Hardware Installation and Reference Guide OL 23069 07 ...