Grounding the PIU
To ground the PIU, follow these steps:
Step 1
Unscrew the two M6 nuts that hold the grounding lug to the PIU and remove the grounding lug from the
PIU.
Step 2
Use a wire-stripping tool to remove approximately 0.75 inch (19 mm) of the insulation from the end of
the 6 AWG grounding wire that you provide.
Step 3
Insert the stripped end of the grounding wire into the open end of the grounding lug as shown in
Figure 6-1 on page 6-9
.
Step 4
Use the crimping tool to crimp the lug to the 6 AWG grounding wire. Verify that the grounding wire is
securely attached to the grounding lug by attempting to pull the wire out of the crimped lug.
Step 5
Secure the grounding lug to the grounding pad threaded studs with the two M6 nuts and tighten them to
40 in-lb (4.5 N·m).
Figure 6-14
shows the location of the grounding pads on the PIU. Ensure that the
grounding lug and the grounding wire do not interfere with other PIU equipment.
1
On each side, fasten two M6 x 19 mm or two
12-24 x 3/4 inch screws (total of four screws
for the PIU) and tighten to 40 in-lb (4.5 N·m).