10.2.- RELAY DIGITAL INPUTS/OUTPUTS
General features
Maximum power of the module
3 W
Refresh time
1 s
Response time (outputs) / Detection time (inputs)
< 150 ms
Relay digital outputs
(95)
Quantity
8
Maximum voltage, open contacts
250 V~
Maximum current
3 A
Maximum switching power
750 VA
Electrical working life (250 VAC / 3A)
10
5
cycles
Mechanical working life
2 x 10
7
cycles
Digital inputs
(95)
Quantity
8
Type
Potential-free contact
Insulation
4 kV
Input impedance
32 kΩ
Environmental features
Operating temperature
-10ºC ... +50ºC
Storage temperature
-20ºC ... +80ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
(96)
IP30
Mechanical features
Dimensions
(mm)
Weight
105 g
Enclosure
V0 self-extinguishing plastic
Assembly
Panel
(95)
Must be connected to SELV circuit.
(96)
This pollution degree hasn’t been tested by UL.
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 1: General requirements
IEC/EN 61010-1:2010
(Third Edition)
Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Im-
munity for industrial environments
UNE-EN 61000-6-2:2006
Electromagnetic compatibility (EMC) -- Part 6-4: Generic standards -
Emission standard for industrial environments
UNE-EN 61000-6-4:2007
Insulation coordination for equipment within low-voltage systems -- Part
1: Principles, requirements and tests�
IEC 60664-1:2007
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 2-030: Particular requirements for testing and
measuring circuits
IEC 61010-2-030:2010
(First Edition)
Safety requirements for electrical equipment for measurement, control,
and laboratory use - Part 1: General requirements
UL 61010-1 3rd edition, 2012-
05
Safety Requirements for Electrical Equipment for Measurement, Control
and Laboratory Use - Part 1: General Requirements (Adopted IEC 1010-
1:1990 with modifications)
CAN/CSA-C22.2 No. 61010-
1, 3rd edition, 2012-05
356
CVM-A1000 - CVM-A1500
Instruction Manual
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...