for this mode simultaneously.
(59)
the characters must be sent in hexadecimal.
Note:
The 11 registers must be written and read at once (as a group), otherwise it will respond
with an error.
6�3�10�16�- Integrated communications
These parameters occupy 1 register each.
Table 64:
Modbus memory map: Configuration variables (Communications)
Communications
Configuration variable
Address
Valid data window
Default value
Protocol
2738
0
: Modbus ,
1
: BACnet
0
Peripheral number
2739
0
to
255
1
Speed
273A
0
: 1200 -
1
: 2400
-
2
: 4800
3
: 9600 -
4
: 19200
-
5
: 38400 -
6
: 57600 -
7
: 76800 -
8
: 115200
4
Parity
273B
0
: No parity
1
: Odd parity
2
: Even parity
0
Length
273C
1
: 8 bits
1
Stop bits
273D
0
: 1 stop bit
1
: 2 stop bits
0
Note:
The 6 registers must be written at once (as a group), otherwise it will respond with an
error.
6�3�10�17�-
Módulo Datalogger
Table 65: Modbus memory map: : Datalogger module (Table 1)
TCP parameters
Configuration variable
Address
Valid data margin
Example
DHCP Flag
E2AE
0
: Deactivation
1
: Activation
-
IP Address
E290 - E291
1 long : 4 characters
AC109C4B (172.16.156.75)
Subnet Mask
E292 - E293
1 long : 4 characters
FFFFF000 (255.255.240.0)
Gateway
E294 - E295
1 long : 4 characters
AC109601(172.16.150.1)
MAC
E2A0 - E2A2 3 integers : 6 characters 14A62C001D54 (14.A6.2C.00.1D.54)
Table 66:Modbus memory map: : Datalogger module (Table 2)
Port address and versions
Configuration variable
Address
Valid data margin
Port
E296 - E297
1 long
Embedded version
E298 - E29B
4 integers : 8 characters
PowerStudio version
E29C - E29F
4 integers : 8 characters
249
Instruction Manual
CVM-A1000 - CVM-A1500