Figure 30: Example of Quality events�
Overvoltage
The
t0
time interval in
shows an overvoltage event. The duration of the event is equal
to the time during which the signal is above the configured threshold value (
), in this example, it is 110% of the rated voltage, plus the time the signal takes to lower
the value, including a 2% hysteresis.
Voltage gap
The
t1
and
t3
time intervals in
show the voltage gaps. The duration of the event is
equal to the time during which the signal is below the configured threshold value (
), in this example, it is 90% of the rated voltage.
Voltage interrupt
The
t2
time interval in
shows an outage or interruption event. The duration of the
event is equal to the time during which the signal is below the configured threshold value
(
), in this example, it is 10% of the rated voltage, plus the time the
signal takes to increase the value, including a 2% hysteresis
Transients
Transients are detected by checking that the difference between a sample and the next one
does not exceed the maximum nominal ramp, multiplied by the coefficient of the distortion level
selected by the user (
In our case, 128 samples are checked per cycle.
The maximum nominal ramp is the value of the maximum tangent, calculated from a nominal
value selected by the user. By definition, this maximum ramp occurs in a sine wave at the ze-
ro-crossing point, so we calculate the sine wave value between sampling point 0 (zero-cross-
ing) and point 1 (first sample) as the maximum ramp.
Transients are checked and saved from phase to phase. The 3 voltage phases are checked
separately and the transient that causes the 6 wave shape cycles of the variable that caused
the transient will be detected.
39
Instruction Manual
CVM-A1000 - CVM-A1500
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...