Table 47 (Continuation):
Configuration of local time
Local time parameter
Local time
Value
Local time
Value
UTC+3
0x0002
UTC-9
0x000E
UTC+4
0x0003
UTC-8
0x000F
UTC+5
0x0004
UTC-7
0x0010
UTC+6
0x0005
UTC-6
0x0011
UTC+7
0x0006
UTC-5
0x0012
UTC+8
0x0007
UTC-4
0x0013
UTC+9
0x0008
UTC-3
0x0014
UTC+10
0x0009
UTC-2
0x0015
UTC+11
0x000A
UTC-1
0x0016
UTC+12
0x000B
UTC
0x0017
6�3�10�3�- Language
This parameter occupies 1 register.
Table 48:
Modbus memory map: Configuration variables (language).
Language
Configuration variable
Address
Valid data window
Default value
Device language
2A9C
0
: Spanish -
1
: English
2
: German -
3
: French
4
: Chinese -
5
: Korean
6
: Norwegian -
7
: Catalan
8
: Italian -
9
: Portuguese
10
: Turkish -
11
: Russian
1
6�3�10�4�- Access key
The
Enable
configuration variable occupies 1 register.
The
Value
configuration variable occupies 4 registers.
Table 49:
Modbus memory map: Configuration variables (Access key).
Access key
Configuration variable
Address
Valid data window
Default value
Enabled
2A97
0
: Enabled
1
: Disabled
1
Value
2A98-2A9B
0
-
9
0x0001 0x0009
0x0007 0x0003
Note:
The 5 registers must be written at once (as a group), otherwise it will respond with an
error
.
242
CVM-A1000 - CVM-A1500
Instruction Manual
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...