9�- TECHNICAL FEATURES
AC power supply ( CVM-A1000-ITF, CVM-A1500-ITF )
Rated voltage
100 ... 240 V ~
Frequency
45 ... 65 Hz
Consumption
CVM-A1000-ITF
max. 23.9 VA
CVM-A1500-ITF
max. 29.4 VA
CVM-A1x00-FLEX
15 ... 22 VA
Installation category
CAT III 300 V
DC Power supply
Rated voltage
CVM-A1x00-ITF-SDC
CVM-A1x00-FLEX-SDC
20 ...120 V
CVM-A1x00-ITF
CVM-A1x00-FLEX
120 ...300 V
Consumption
CVM-A1000-xxx-SDC
max. 10.6 W
CVM-A1500-xxx-SDC
max. 13.8 W
CVM-A1000-ITF
max. 12.2 W
CVM-A1500-ITF
max. 11.9 W
CVM-A1x00-FLEX
8 ... 10 W
Installation category
CAT III 300 V
Voltage measurement circuit
Standard
BOLD terminals
Voltage measurement margin
20 ... 600 V ~
20 ... 300 V ~
Frequency measurement margin
40 ... 70 Hz
Input impedance
1.2 M
Ω
Minimum measurement voltage (Vstart)
10 V ~
Maximum voltage input consumption
0.15VA
Installation category
CAT III 600 V
CAT III 300 V
Current measurement circuit (CVM-A1x00-ITF)
Nominal current (In)
.../5A , .../1A or .../0.250 A
Phase current measurement margin
In: ���/5A
In: ���/1A
In: ���/0�250A
0.01...10A
0.01...2A
0.01 ...0.5A
Neutral current measurement margin
���/5A
���/1A
���/A
(calculated)
0.02 ...10A
0.02...2A
0.02 ... 10A (
In: ���/5A
)
0.02 ... 2A (
In: ���/1A
)
0.02 ... 0.5A(
In: ���/0�250A
)
Maximum current, impulse < 1s
100 A
Minimum measurement current (Istart)
0.01 A
0.01 A
0.01 A
Maximum current input
consumption
0.9 VA
Installation category
Standard
BOLD terminals
CAT III 600 V
CAT III 300 V
Current measurement circuit (CVM-A1x00-FLEX)
Measure through Rogowsky sensors
Nominal current (In)
1000 /100 mV~
Current measurement margin
10 ... 120 % In
Minimum measurement current (Istart)
10 A
350
CVM-A1000 - CVM-A1500
Instruction Manual
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...