Table 138: Modbus memory map: Analogue inputs, expansion modules (Table 3)�
Configuration of analogue inputs: Slot 2
Configuration variable
Address
Input 1
Input 2
Input 3
Input 4
Zero
D6D8
D6EC
D700
D714
Full-scale
D6D9
D6ED
D701
D715
Scale
D6DA
D6EE
D702
D716
No. of decimals
D6DB
D6EF
D703
D717
Input name
D6DC - D6DF D6F0 - D6F3
D704 - D707
D718 - D71B
Units
D6E0 - D6E2
D6F4 - D6F6
D708 - D70A D71C - D71E
Note:
The 11 registers must be written and read at once (as a group), otherwise it will respond
with an error.
Table 139: Modbus memory map: Analogue inputs, expansion modules (Table 4)�
Configuration of analogue inputs: Slot 3
Configuration variable
Address
Input 1
Input 2
Input 3
Input 4
Zero
DAC0
DAD4
DAE8
DAFC
Full-scale
DAC1
DAD5
DAE9
DAFD
Scale
DAC2
DAD6
DAEA
DAFE
No. of decimals
DAC3
DAD7
DAEB
DAFF
Input name
DAC4 - DAC7 DAD8 - DADB DAEC - DAEF DB00 - DB03
Units
DAC8 - DACA DADC - DADE DAF0 - DAF2 DB04 - DB06
Note:
The 11 registers must be written and read at once (as a group), otherwise it will respond
with an error.
Table 140: Modbus memory map: Analogue inputs, expansion modules (Table 5)�
Configuration of analogue inputs: Slot 4
Configuration variable
Address
Input 1
Input 2
Input 3
Input 4
Zero
DEA8
DEBC
DED0
DEE4
Full-scale
DEA9
DEBD
DED1
DEE5
Scale
DEAA
DEBE
DED2
DEE6
No. of decimals
DEAB
DEBF
DED3
DEE7
Input name
DEAC - DEAF
DEC0 - DEC3 DED4 - DED7 DEE8 - DEEB
Units
DEB0 - DEB2
DEC4 - DEC6 DED8 - DEDA DEEC - DEEE
Note:
The 11 registers must be written and read at once (as a group), otherwise it will respond
with an error.
305
Instruction Manual
CVM-A1000 - CVM-A1500
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...