Phase-phase voltage
L
= Primary rated voltage* 0.9 * √3
H
=
Primary rated voltage * 1.1 * √3
Min
=
L
* 0.8
Max
=
H
* 1.2
P
L
=
L
+ ((
H
-
L
) * 0.1)
P
H
=
H
- ((
H
-
L
) * 0.1)
Current
L
= 0
H
= Primary current
Min
= 0
Max
=
H
* 1.2
P
L
= 0
P
H
=
H
- ((
H
-
L
) * 0.1)
The alarm and pre-alarm zones L are not displayed.
Power ratings
L
= 0
H
= Primary rated voltage * Primary current
Min
= 0
Max
=
H
* 1.2
P
L
= 0
P
H
=
H
- ((
H
-
L
) * 0.1)
The alarm and pre-alarm zones L are not displayed.
Frequency 50 Hz
L
= 45
H
= 55
Min
=
L
* 0.95
Max
=
H
* 1.05
P
L
=
L
+ ((
H
-
L
) * 0.25)
P
H
=
H
- ((
H
-
L
) * 0.25)
Frequency 60 Hz
L
= 55
H
= 65
Min
=
L
* 0.95
Max
=
H
* 1.05
P
L
=
L
+ ((
H
-
L
) * 0.25)
P
H
=
H
- ((
H
-
L
) * 0.25)
Voltage THD
L
= 0
H
= 5
Min
=0
Max
=
H
* 2
P
L
=
L
+ ((
H
-
L
) * 0.25)
P
H
=
H
- ((
H
-
L
) * 0.25)
The alarm and pre-alarm zones L are not displayed.
Current THD
L
= 0
H
= 20
Min
=0
Max
=
H
* 2
P
L
=
L
+ ((
H
-
L
) * 0.25)
P
H
=
H
- ((
H
-
L
) * 0.25)
The alarm and pre-alarm zones L are not displayed.
51
Instruction Manual
CVM-A1000 - CVM-A1500
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...