7�6�4�- MODBUS COMMUNICATIONS
Table 152:Modbus memory map: LonWorks communications module
Configuration of the LonWorks parameters
Configuration variable
Address
Valid data margin
Default value
Flag Service Pin
(88)
E678
0
-
1
( Function 0x10)
1
(Function 0x04)
-
Neuron ID
(89)
E67A - E67C
Decimal value
-
(88)
The following functions are implemented for this variable:
Function 0x04
: reading registers.
Function 0x10
: Writing multiple registers.
(89)
For this variable
Function 0x04
is implemented.
7�6�5�- LIST OF LONWORKS LOGS
Note:
The binary files and setup file can be downloaded from
Circutor’s
website.
Variable
Name
Variable type
Unit
Current L1
nvo_Ph1Current
SNVT_amp_ac (139)
A 1
Code
Resolution
Values
02
1
0..65,534
Current L2
Name
Variable type
Unit
nvo_Ph2Current
SNVT_amp_ac (139)
A 2
Code
Resolution
Values
07
1
0..65,534
Current L3
Name
Variable type
Unit
nvo_Ph3Current
SNVT_amp_ac (139)
A 3
Code
Resolution
Values
12
1
0..65,534
Phase-Phase Voltage V12
Name
Variable type
Unit
nvo_Ph2PhU12
SNVT_volt_ac (138)
V 12
Code
Resolution
Values
22
1
0..65,534
Phase-Phase Voltage V23
Name
Variable type
Unit
nvo_Ph2PhU23
SNVT_volt_ac (138)
V 23
Code
Resolution
Values
23
1
0..65,534
Phase-Phase Voltage V31
Name
Variable type
Unit
nvo_Ph2PhU31
SNVT_volt_ac (138)
V 31
Code
Resolution
Values
24
1
0..65,534
Phase-Neutral Voltage L1
Name
Variable type
Unit
nvo_Ph2NU1
SNVT_volt_ac (138)
V 1
Code
Resolution
Values
01
1
0..65,534
Phase-Neutral Voltage L2
Name
Variable type
Unit
nvo_Ph2NU2
SNVT_volt_ac (138)
V 2
Code
Resolution
Values
06
1
0..65,534
318
CVM-A1000 - CVM-A1500
Instruction Manual
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...