10.3.- ANALOGUE INPUTS/OUTPUTS
General features
Maximum power of the module
3W
Refresh time
1 s
Response time (outputs) / Detection time (inputs)
< 150 ms
Analogue outputs
(97)
Quantity
8
Maximum internal voltage
12 V
Linearity
<1%
DAC resolution
4096 dots
Analogue outputs in current mode
Nominal output range
0-20 mA or 4-20 mA (Programmable)
Maximum load resistor
300
Ω
Analogue outputs in voltage mode
Nominal output range
0-10 V
Minimum load resistor
5000
Ω
Analogue inputs
(97)
Quantity
4
Type of measurement
Current
Nominal input range
0-20 mA or 4-20 mA (Programmable)
Accuracy
<1%
Input impedance
150
Ω
Maximum acceptable input current
22 mA
Environmental features
Operating temperature
-10ºC ... +50ºC
Storage temperature
-20ºC ... +80ºC
Relative humidity (without condensation)
5 ... 95%
Maximum altitude
2000 m
Protection degree
(98)
IP30
Mechanical features
Dimensions
(mm)
Weight
80 g
Enclosure
V0 self-extinguishing plastic
Assembly
Panel
(97)
Must be connected to SELV circuit.
(98)
This pollution degree hasn’t been tested by UL.
Standards
Safety requirements for electrical equipment for measurement, control
and laboratory use -- Part 1: General requirements
IEC/EN 61010-1:2010
(Third Edition)
Electromagnetic compatibility (EMC) -- Part 6-2: Generic standards - Im-
munity for industrial environments
UNE-EN 61000-6-2:2006
Electromagnetic compatibility (EMC) -- Part 6-4: Generic standards -
Emission standard for industrial environments
UNE-EN 61000-6-4:2007
Insulation coordination for equipment within low-voltage systems -- Part
1: Principles, requirements and tests�
IEC 60664-1:2007
357
Instruction Manual
CVM-A1000 - CVM-A1500
Summary of Contents for CVM-A1000
Page 2: ...2 CVM A1000 CVM A1500 Instruction Manual...
Page 364: ...13 CE CERTIFICATE 364 CVM A1000 CVM A1500 Instruction Manual...
Page 365: ...365 Instruction Manual CVM A1000 CVM A1500...
Page 366: ...366 CVM A1000 CVM A1500 Instruction Manual...