7�9�5�- MODBUS COMMUNICATIONS
The following functions are implemented for these variables:
Function 0x04
: reading registers.
Function 0x10
: Writing multiple registers.
7.9.5.1.- Configuration of DHCP activation/deactivation
Table 175:Modbus memory map: Modbus TCP (Switch) communications module (Table 1)
Configuration of DHCP activation/deactivation
Configuration variable
Address
Valid data margin
Default value
DHCP Flag
F23A
0
: Deactivation
1
: Activation
1
7.9.5.2.- Configuration of the TCP parameters
Table 176:Modbus memory map: Modbus TCP (Switch) communications module (Table 2)
Configuration of the Modbus TCP parameters
Configuration variable
Address
Valid data margin
Default value
IP Address
F230 - F231
1 long : 4 characters
-
Subnet Mask
F232 - F233
1 long : 4 characters
-
Gateway
F234 - F235
1 long : 4 characters
-
Note:
The module resets to activate the configuration.
Note:
The 6 registers must be written at once (as a group), otherwise it will respond with an
error.
7�9�5�3�- MAC address of the Modbus TCP module
The function implemented for this variable is:
Function 0x04
: reading registers.
Table 177:Modbus memory map: Modbus TCP (Switch) communications module (Table 3)
MAC address of the Modbus TCP module
Configuration variable
Address
Valid data margin
MAC address
F236 - F238
3 integers : 6 characters
345
Instruction Manual
CVM-A1000 - CVM-A1500