Raption 50 Series Installation Manual
Mode 3 Charge Controller (A6) is responsible for conducting the Mode 3
communications and allows charging electrical vehicle as defined by IEC 61851
for AC side.
Communication to the device is only possible via RS485 communications through
inputs 1 and 2. The device integrates an Ethernet port, which does not allow
connectivity to TCP/IP networks. It is used for internal use as digital inputs and
outputs.
The default configuration modbus address is set at 96 and baud rate is set to
19200bps.
Item
Name
Function
1
A- RS-485 BUS
Terminal (+)
2
B- RS-485 BUS
Terminal (-)
3
PP- EV Connection
Proximity (PP)
4
CP-EV Connection
Control Pilot (CP)
5
RL- Contactor
Contactor coil
6
A1- Power Supply
Phase
7
A2- Power Supply
Neutral
8
Ground
Ground
Mode 3 Device
D
Raption 50 Series Service Manual