34
ENGLISH
2 - STORAGE
• Store the heat exchangers in a dry room protected from the weath-
er and maintained at a temperature b5°C and +35°C.
• The heat exchangers must be placed on blocks dimensioned
and adjusted to ensure adequate stability and levelness, on
a floor protected from caving in. Make sure that they do not
touch each other and that they are not in direct contact with
the floor and any walls.
• Protect them from impacts, dust and from the risk of liquid or
solid deposits and make sure that nothing is placed on them.
• Do not remove the protection on the end of the pipes until
you are ready to make the hydraulic connections.
• All unused spare parts must be stored away from damp,
light, and dust, and protected from impacts.
• Gaskets and gasketed plates must be stored in appropriate
boxes at a temperature of between 10°C and 30°C. Maxi-
mum shelf-life: 12 months from the invoice.
3 - INSTALLATION
Always read this guide carefully before working on the
unit and keep it in a safe place for future reference.
3.1 - Choice of location
The intended location of the unit should be fully accessible so as
to ease servicing and maintenance operations and allow easy
removal of the plates from the side of the unit (Fig. 3). Adequate
clearance must be left in front of the safety and control devices.
minimum recommended
value (mm)
Model
A
DN32
700
DN50
1000
DN65
1000
DN100
1500
DN150
1500
DN200
2000
Fig. 3
A
3.2 - Installation recommendations
• CIPRIANI plate heat exchangers have a limited operating
pressure and temperature range. Install all the necessary
safety devices to prevent overrunning the limits specified
on the order documents. Approval to use the plate heat
exchangers at higher conditions must be obtained from CIP-
RIANI. It is recommended to fit pressure and temperature
test points near the unit.
• Make sure that the heat exchanger is compliant with the
safety rules in force on the site of use (explosive atmos-
phere, etc.).
• Affix appropriate visual warning sign wherever the surface
temperature above 60°C or below 0°C.
• If the heat exchanger is to be installed on framework, the
Summary of Contents for S020+
Page 124: ...124 1 2 60 C CIPRIANI CIPRIANI PED 2014 68 PED 2014 68 CIPRIANI...
Page 125: ...125 RU CIPRIANI...
Page 126: ...126 0 C CIPRIANI CIPRIANI 1 1b 2...
Page 127: ...127 RU 1a 1b 2...
Page 128: ...128 1 2 3 4 5 6 7 8 9 10 11 12...
Page 129: ...129 RU TS PS PT PED 2014 68 CE PED 2014 68 I II III IV CE II III IV 1 2 d d...
Page 131: ...131 RU 60 C 0 C 60 C 500 5 7 4 2 4...
Page 132: ...132 TF PB...
Page 133: ...133 RU CIPRIANI 10...
Page 134: ...134 1 2 3 4 1 2 3 4 4 1 5 CIPRIANI 1 2 3 4 11 5 6 Plug In...
Page 136: ...136 1 2 40 C 3 4...
Page 138: ...138 CIPRIANI 6 Plug In 7 Plug In Plug In 8 Plug In 5 7 1 A 7 6...
Page 139: ...139 RU Plug In 9 b 5 7 3 Plug In Plug In 9 5 7 3 Plug In 5 7 1 Plug In DN200 2 3 5 2 ACS 8 9...
Page 140: ...140 10 11 CIPRIANI PS 10 Fig 10 Fig 11...
Page 144: ...144 CIPRIANI CIPRIANI...
Page 145: ...145 RU CIPRIANI NBR EPDM FPM HNBR...
Page 146: ...146 Note...
Page 147: ...147 Note...