![Chroma 62000L Series User Manual Download Page 36](http://html1.mh-extra.com/html/chroma/62000l-series/62000l-series_user-manual_2604533036.webp)
Programmable DC Power Supply 62000L Series User’s Manual
3-4
exceeded, the power supply will automatically adjust the constant voltage,
and the output current will drop in proportion.
3. When the VA value from setting the meter mode or the limit mode exceeds
the rated power like 108W on the 62010L-36-7, or 150W on the 62015L-60-6,
the limit signal on the display will flash until you decrease the voltage or the
current in order to set the power lower than the rated value.
Remote Operation:
VOLTage {<voltage> |MIN|MAX}
This command sets the voltage.
CURRent {<current> |MIN|MAX}
This command sets the current.
OUTPut ON
This command is applied to enable the output.
3.3
Storing and Recalling Operation States
The power supply can remember 16 different operating states in non-volatile memory. An
operating state contains CV limit, CC limit, OVP trip level, OVP ON/OFF state, OCP trip level
and OCP ON/OFF state. Location 0 is the power-on state. You can recall one of the saved
states through the front panel or remote control. The reset state (62010L-36-7’s factory
default - OVP Level: 39.6V/OVP ON/OCP Level: 7.7A/OCP ON/Voltage Limit: 0V/Current
Limit: 3A) is initially saved in the locations from 0 to 15. You might use the following
procedures to store and recall an operating state.
Note
The 62015L-60-6 has the factory default, OVP Level: 66V/OVP ON/OCP Level:
6.6A/OCP ON/Voltage Limit: 0V/Current Limit: 6A.
Storing an Operating State via the Front Panel
1. Press the
Store
button.
2. Rotate the knob and select a location from 0 to 15, where you want to save your settings.
You can use
or
buttons to review the settings stored in the selected location.
3. Press the
Store
button to store active operating state. If you want the settings you define
as the power-on state, save your settings in Location 0.
4. To abort the storing operation, press any other button except the Store button.
Recalling a Stored State via the Front Panel
1. Press the
Recal
l button.
2. Rotate the knob and select the stored location you want. You can use
or
buttons to
review the settings stored in the selected location.
3. Press the
Recall
button once again to recall the stored settings.
4. To abort the recall operation, press any other button except the Recall.
Remote Operation:
*SAVE {0|1|…|15}
Save an operating state to a specified location.
*RCL {0|1|…|15}
Recall a stored state from a specified location.