11-8
11.5. Programming Alarms
Alarm parameters (alarm types, alarm value, etc.) can be programmed for each alarm point (channel, level).
By programming alarm parameters, display of alarm-on and printings of alarm-on/reset can be executed.
The [alarm parameters] programming display appears by pressing + keys.
1. Alarm parameters
The default is "alarms not programmed".
1) Alarm points (channels, levels)
Alarm points can be programmed maximum 4
levels every channel.
2) Alarm types
Alarm types can be selected every alarm point
out of six kinds shown below.
Absolute
value
:Higher-limit
alarm
:Lower-limit
alarm
Rate-of-
change
:Increase-limit
alarm
:Decrease-limit
alarm
Differential
:Differential
higher-limit
alarm
:Differential
lower-limit
alarm
3) Alarm value
A desired alarm generation value.
4) Others
・
Rate-of-change alarm…..Program measuring count (1 to 9).
・
Differential alarm……….Program channels to be compared.
2. Alarm types
The higher-limit alarm of an absolute value alerts when alarm value
≦
measured value, while the
lower-limit alarm alerts when measured value
≦
alarm value.
For the rate-of-change alarm and differential alarm operations, refer to the following figure.
Increase-limit alarm: Change width (PV2-PVl)
per unit time (
Δ
t) is plus.
Decrease-limit alarm: Change with (PV2-PV1)
per unit time (
Δ
t) is minus.
Unit time(
Δ
t) =
Measuring interval
×
measuring count (1 to 9)
*Minus symbol is not attached to the alarm value
of decrease-limit alarm(
).
Rate-of-change alarm
0
Increase-limit
alarm-on
Decrease-limit
alarm-on
alarm value
alarm
value*
U
D
+
-
Change
width
Δ
t
Differential higher-limit alarm alerts when
difference (absolute value) of measured values
≧
alarm value
Differential lower-limit alarm alerts when
difference (absolute value) of measured values
≦
alarm value
Differential alarm
Difference of
measured value
(absolute value)
Alarm-on
(Differential
higher-limit alarm)
Alarm-on
(Differential
lower-limit alarm)
Alarm
value
Alarm
value
Difference of measured
value (absolute value)
○
1
The above figure shows programming alarm
points up to level 4 on channel 1.
○
2
Alarm is on at level 2 (higher limit) as the
measured value (55) is higher than alarm value
(50).
*Standard specifications have no alarm output.
[0]-fixed
Relation between alarm parameters and alarm
1
2
H
0
50
1
3
H
0
60
1
4
H
0
70
1
1
L
0
35
0
100
(55)
Measured value
…Channel
…Level
…Alarm types
…(Output number)
*
…Alarm value
Alarm
point
Alarm
specifications
- In case of absolute value alarm -