78
Functionality
CG Drives & Automation, 01-5980-01r2
Used Thermal Capacity [2314)
This menu shows the used thermal capacity of the motor, i.e.
the actual I
2
t value divided by the maximum I
2
t value,
expressed in (%) .
PT100 Alarm[232]
The PT100 menus are only shown if a PT100 option board
is connected.
PT100 Alarm Action [2321]
Motor Class [2322]
Only visible if the PTC/PT100 option board is installed. Set
the class of motor used. The trip levels for the PT100 sensor
will automatically be set according to the setting in this
menu.
PT100 Inputs [2323]
Two PT100 option boards (B1 and B2) may be connected,
enabling up to six PT100 inputs. With menu [2323] “PT100
Inputs”, you can select which PT100 inputs that should be
supervised, i.e. which are allowed to generate a trip/warning
when the temperature exceeds the limit set in menu [2322]
“Motor Class”.
PT100 input 1, 2 and 3 are equal to input terminal 1, 2 and
3 on the first PT100 option board (B1). PT100 input 4, 5
and 6 are equal to input terminal 1, 2 and 3 on the second
PT100 option board (B2).
Note that the supervised inputs must be selected in a
sequence without gaps, i.e. if you like to have only one input
supervised (selection PT100 1) you must use input 1 on
board one (B1).
If you wish to have four PT100 inputs supervised (selection
PT100 1-4) you must use input 1-3 on option board one
(corresponding to input 1-3) and the first input of board 2
(corresponding to input 4).
All PT100 inputs are displayed in operation menu [71B]
PT100 B1 1, 2, 3 and [71C] PT100 B2 1, 2, 3, regardless of
the menu selection.
PTC Alarm [233]
The PTC alarm menus are always shown as there is an
integrated PTC input on the power board (PB-PTC)
terminal 69 and 70, as standard.
PTC Alarm Action [2331]
Read-only
Default:
No Action
No Action
0
For a definition, see Table 23, page 55
Hard Trip
1
Soft Trip
3
Warning
4
Default:
F 140°C
A 100°C
0
E 115
°
C
1
B 120
°
C
2
F 140
°
C
3
F Nema
145
°
C
4
H 165°C
5
2314 Used Th Cap
Stp
M1:
XX%
2321 PT100 AA
Stp
M1:
No Action
2322 Motor Class
Stp
M1:
F 140
o
C
Default:
PT100 1-3
PT100 1
0
Channel 1 used for PT100 protection
PT100 1-2 1
Channel 1-2 used for PT100 protection
PT100 1-3 2
Channel 1-3 used for PT100 protection
PT100 1-4 3
Channel 1-4 used for PT100 protection
PT100 1-5 4
Channel 1-5 used for PT100 protection
PT100 1-6 5
Channel 1-6 used for PT100 protection
Default:
No action
No action
0
For a definition, see Table 23, page 55.
Hard Trip
1
Soft Trip
3
Warning
4
2323 PT100Inputs
Stp
M1:
PT100 1-3
2331 PTC AA
Stp
M1:
No action
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......