CG Drives & Automation, 01-5980-01r2
Functionality
117
The output signal can be programmed as a virtual
connection source and to the relay outputs.
Example:
An analogue level sensor with current signal, 4-20 mA, is
connected to the analogue input. See table below.
When the signal on AnIn goes above 60%, the CA output
signal is activated (high), and when the signal on AnIn goes
below 40%, the CA output signal is deactivated (low) again.
The output of CA1 is used as a virtual connection source that
controls the virtual connection destination Run FWD.
Fig. 66
Default:
Current
Process Val
0
Torque
1
%
Shaft Power
2
kW
El Power
3
kW
Current
4
A
Heatsink Tmp 5
°C
PT100_1
6
°C
PT100_2
7
°C
PT100_3
8
°C
Energy
9
kWh
Run Time
10
h
Mains Time
11
h
AnIn
12
%
PT100_4
13
°C
PT100_5
14
°C
PT100_6
15
°C
Menu
Function
Setting
21A
Level/Edge
Level
511
AnIn Function
Process value
512
AnIn Setup
4-20 mA
522
DigIn2
Off
6111
CA1 Value
AnIn
6112 CA1 Level HI
60% (12 mA/20 mA x 100%)
6113 CA1 Level LO
40% (8 mA/20 mA x 100%)
6114
CA1 Type
Hysteresis
561
VIO 1 Dest
Run FWD
562
VIO 1 Source
CA1
6111 CA1 Value
Stp
Current
No.
Description
1
The reference signal passes the Level LO value from
below (positive edge), the comparator CA1 output stays
low, mode = STOP.
2
The reference signal passes the Level HI value from
below (positive edge), the comparator CA1 output is set
high, mode = RUN.
3
The reference signal passes the Level HI value from
above (negative edge), the comparator CA1 output stays
high, mode = RUN.
4
The reference signal passes the Level LO value from
above (negative edge), the comparator CA1 output =
STOP.
t [s]
CA1 Level HI
CA1 Level LO
Signal AnIn
CA1
Mode
RUN
STOP
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......