CG Drives & Automation, 01-5980-01r2
Functionality
113
Fig. 63 Relay function example for start and braking cycle.
CTR2
61
Counter output 2.
!CTR2
62
Counter output 2 inverted.
CLK1
63
Clock output 1 (Clock logic [660]).
!CLK1
64
Clock output 1 inverted.
CLK2
65
Clock output 2 (Clock logic [660]).
!CLK2
66
Clock output 2 inverted.
Run Signal
67
Run command is active.
Loc/Rem
68
Local/Rem mode indication
Local = 1, Remote = 0
Acc
69
Motor Accelerating
Dec
70
Motor Decelerating
DigIn 1
71
Digital input 1 active
DigIn 2
72
Digital input 2 active
DigIn 3
73
Digital input 3 active
DigIn 4
74
Digital input 4 active
RunSignalFWD 75
Copy of input start command signal
Run FWD. For contactor control when
reverse current braking used, see
chapter 3.4 Example 3.
RunSignalREV 76
Copy of input start command signal
Run REV. For contactor control when
reverse current braking used with
reverse direction operation.
OperationFWD 77
Motor running in forward (+) /
clockwise direction. Used for the
forward contactor control in fwd/rev
applications.
Note! Active during jog in any
direction.
OperationREV 78
Motor running in reverse (-)
/
counter
clockwise direction. Used for the
reverse contactor control in fwd/rev
applications.
ManRst Trip
79
Any active trip condition that needs a
manual reset
Trip (ex LM)
81
A trip condition is active (except load
monitor)
Overvolt
90
Overvoltage alarm active (trip or
warning)
Com Error
97
Communication error active (trip or
warning)
Com Active
98
Fieldbus communication active.
Overtemp
101
Softstarter overtemperature condition
is active (trip)
PTC Alarm
103 PTC alarm active (trip or warning)
PT100 Alarm
104 PT100 alarm active (trip or warning)
I
2
t
105 I
2
t alarm active (trip or warning)
Ext Alarm 1
106 Ext Alarm 1 active
Ext Alarm 2
107 Ext Alarm 2 active
At Zero Spd
113
Zero speed detection signal
calculated by control software.
Activated only when motor standstill
has been detected after braking to
stop.
This Zero speed detection only works
if stop method Brake or Spin brake is
selected.
Note: Signal does not indicate
standstill at power on.
Supply Fault
114
Sum alarm for supply voltage.
Activated if
Multi/Phase fault,
Over/Under voltage or
phase reversal (trip or warning).
Note! Trips are latched until reset..
Bypass mode
Motor voltage
Operation
Run signal
Stop time
Start time
Delay
Full voltage
RevCurrBrake
At Zero Spd
Zero Speed
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......