Functionality
105
Under-Voltage Alarm [433]
In this menu group the settings for an undervoltage alarm are
selected.
Under-Voltage Alarm Action [4331]
In this menu the alarm action for the undervoltage alarm is
selected. The following alarm actions are available:
Under-Voltage Level [4332]
Here the voltage level for an undervoltage alarm is entered,
expressed as a percentage of the nominal motor voltage. As
soon as any line voltage falls below this voltage level for a time
period equal to the set delay time in menu [4333], an
undervoltage alarm will occur and the action selected in
menu [4331] will be executed.
Under-Voltage Alarm Delay [4333]
In this menu the response delay for the voltage unbalance
alarm, as set in [4431] and [4432], is selected
Phase Reversal Alarm [434]
If this function is activated, an alarm will be issued if the
wrong phase sequence is detected prior to a start.
Phase Reversal Alarm Action [4341]
In this menu the alarm action for a phase reversal alarm is
selected. The softstarter will detect the phase sequence prior
to each start attempt. If the actual phase sequence does not
match the allowed phase sequence set in menu [4342], the
action chosen in this menu will be executed.
To enable the phase reversal alarm, a motor has to be
connected and the mains voltage has to be switched on. The
alarm is only valid at starting attempts.
Allowed Phase Sequence [4342]
In this menu the allowed phase sequence is selected.
Default:
No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip
1
Soft Trip
3
Warning
4
Default:
85% of nominal motor voltage [221].
Range:
75 - 100% of nominal motor voltage [221].
Default:
1s
Range:
1 - 90 s
4331 UnderVolt AA
Stp
No Action
4332 UnderV Level
Stp
85%
4333 UnderV Del
Stp
1s
Default:
No Action
No Action 0
For a definition, see Table 23, page 55.
Hard Trip
1
Soft Trip
3
Warning
4
Default:
L123
Selection:
L123 and L321
4341 PhaseRevAA
Stp
No Action
4342 AllowedSequ
Stp
L123
Summary of Contents for emotron TSA Series
Page 1: ...Emotron TSA Softstarter Instruction manual English Valid from Software version 1 27...
Page 2: ......
Page 4: ......
Page 6: ...2 CG Drives Automation 01 5980 01r2...
Page 12: ...8 Introduction CG Drives Automation 01 5980 01r2...
Page 18: ...14 Mounting CG Drives Automation 01 5980 01r2...
Page 42: ...38 Application guidelines CG Drives Automation 01 5980 01r2...
Page 46: ...42 Getting started CG Drives Automation 01 5980 01r2...
Page 70: ...66 Main features CG Drives Automation 01 5980 01r2...
Page 142: ...138 Functionality CG Drives Automation 01 5980 01r2...
Page 158: ...154 Troubleshooting Diagnoses and Maintenance CG Drives Automation 01 5980 01r2...
Page 160: ...156 Options CG Drives Automation 01 5980 01r2...
Page 168: ...164 Technical data CG Drives Automation 01 5980 01r2...
Page 202: ...CG Drives Automation 01 5980 01r2 198...
Page 203: ......